Item | Specifications | ||
---|---|---|---|
Rated pressure range | 0 to 1 MPa (gauge pressure) | ||
Measurable fluid | Air (compressed air) | ||
Rated operating voltage | 24 V DC ±10 % | ||
Rated power consumption | 40 mA or less | ||
Pulse output (Pulse output 1 and Pulse output 2) |
Open drain output •Max. inflow current: 10 mA •Applied voltage: 24 V DC or less •Residual voltage: 1 V or less (at inflow current 10 mA) |
||
Output mode | Pulse output 1: Direct flow pulse Pulse output 2: Reverse flow pulse, Flow limit alarm (select by button operation) |
||
Over current protection | Equipped | ||
Pulse output duty | 1:1 (35 to 65 %) | ||
Analog current output | Output current: 4 to 20 mA Output accuracy: ±0.1 mA Max. external load: 400 Ω or less |
||
Output mode | Instant flow, air pressure and temperature (select by button operation) |
||
Instant flow | Zero point: 4 mA (Direct flow display mode, reverse flow ~ within low flow cut off) 12 mA (Direct/Reverse flow display mode, within low flow cut off) |
||
Air pressure | 0 kPa: 4 mA, 1 MPa: 20 mA | ||
Temperature | −10 ℃ +14 ℉: 4 mA, +60 ℃ +140 ℉: 20 mA | ||
Pressure loss | Extremely small (same as straight pipe) |
||
Response time | 500 ms | ||
Enclosure protection | IP64 (IEC) | ||
Ambient temperature | −10 to +60 ℃ +14 to +140 ℉ (Storage: −20 to +70 ℃ −4 to +158 ℉) |
||
Ambient humidity | 90 % RH or less (No dew condensation or icing allowed) |
Small pipe size type
Model No. | AEWA1025 | AEWA1032 | |
---|---|---|---|
Pipe size | 25A (1B) | 32A (1 1/4B) | |
Flow range (actual flow) | −0.6 to −35 m3/h or+0.6 to +35 m3/h | −1.1 to −65 m3/h or+1.1 to +65 m3/h | |
Flow measuring accuracy |
±5 % R.S. | −0.6 to −3.5 m3/h or+0.6 to +3.5 m3/h | −1.1 to −6.5 m3/h or+1.1 to +6.5 m3/h |
±2 % R.S. | −3.5 to −35 m3/h or+3.5 to +35 m3/h | −6.5 to −65 m3/h or+6.5 to +65 m3/h | |
Normal conversion accuracy |
±2.5 % R.S. (at dry air, ordinary temperatures and 0.5 MPa) |
||
Unit for pulse output | 10, 100, 1,000 NL/pulse or L/pulse | ||
Low flow cut off | Within ±0.09 m3/h | Within ±0.16 m3/h | |
Material | Measuring pipe: Aluminum alloy, PPS and phlor silicone rubber | ||
Net weight | 1.5 kg approx. | 1.4 kg approx. | |
Accessories | M4 hexagon wrench: 1 pc |
Medium pipe size type
Model No. | AEWA1040 | AEWA1050 | AEWA1065 | AEWA1080 | |
---|---|---|---|---|---|
Pipe size | 40A (1 1/2B) | 50A (2B) | 65A (2 1/2B) | 80A (3B) | |
Flow range (actual flow) | −1.3 to −80 m3/h or +1.3 to +80 m3/h |
−2.5 to −150 m3/h or +2.5 to +150 m3/h |
−4 to −240 m3/h or +4 to +240 m3/h |
−5 to −300 m3/h or +5 to +300 m3/h |
|
Flow measuring accuracy |
±5 % R.S. | −1.3 to −8 m3/h or +1.3 to +8 m3/h |
−2.5 to −15 m3/h or +2.5 to +15 m3/h |
−4 to −24 m3/h or +4 to +24 m3/h |
−5 to −30 m3/h or +5 to +30 m3/h |
±2 % R.S. | −8 to −80 m3/h or +8 to +80 m3/h |
−15 to −150 m3/h or +15 to +150 m3/h |
−24 to −240 m3/h or +24 to +240 m3/h |
−30 to −300 m3/h or +30 to +300 m3/h |
|
Normal conversion accuracy |
±2.5 % R.S. (at dry air, ordinary temperatures and 0.5 MPa) |
||||
Unit for pulse output | 10, 100, 1,000 NL/pulse or L/pulse | ||||
Low flow cut off | Within ±0.2 m3/h |
Within ±0.4 m3/h |
Within ±0.6 m3/h |
Within ±0.8 m3/h |
|
Material | Measuring pipe: Aluminum alloy, PPS and phlor silicone rubber | ||||
Net weight | 1.0 kg approx. | 1.2 kg approx. | 1.5 kg approx. | 1.7 kg approx. | |
Accessories | Positioning collar: 4 pcs, M4 hexagon wrench: 1 pc, Flange packing: 2 pcs, Bolt set: 1 set (bolt, nut and plain washer) |
Large pipe size type
Model No. | AEWA1100 | AEWA1150 | AEWA1200 | |
---|---|---|---|---|
Pipe size | 100A (4B) | 150A (6B) | 200A (8B) | |
Flow range (actual flow) | −10 to −500 m3/h or +10 to +500 m3/h |
−24 to −1,200 m3/h or +24 to +1,200 m3/h |
−40 to −2,000 m3/h or +40 to +2,000 m3/h |
|
Flow measuring accuracy |
±5 % R.S. | −10 to −50 m3/h or +10 to +50 m3/h |
−24 to −120 m3/h or +24 to +120 m3/h |
−40 to −200 m3/h or +40 to +200 m3/h |
±2 % R.S. | −50 to −500 m3/h or +50 to +500 m3/h |
−120 to −1,200 m3/h or +120 to +1,200 m3/h |
−200 to −2,000 m3/h or +200 to +2,000 m3/h |
|
Normal conversion accuracy |
±2 % R.S. (at dry air, ordinary temperatures and 0.5 MPa) |
|||
Unit for pulse output | 0.1, 1, 10 Nm3/pulse or m3/pulse | |||
Low flow cut off | Within ±2.6 m3/h |
Within ±5.0 m3/h |
Within ±9.0 m3/h |
|
Material | Measuring pipe: Stainless steel alloy, PPS and phlor silicone rubber | |||
Net weight | 10.3 kg approx. | 18.3 kg approx. | 24.4 kg approx. | |
Accessories | Positioning collar: 2 pcs, M4 hexagon wrench: 1 pc |
|
|
|