Business > Industrial Devices > Automation Controls Top > FA Sensors & Components > Pressure Sensors / Flow Sensors > Pressure Sensors / Flow Sensors > Dual Display Digital Pressure Sensor [For Gas] DP-100L > Specifications
|
Type | Discrete wire type | M12 connector type | |||
---|---|---|---|---|---|
For low pressure | For high pressure | For low pressure | For high pressure | ||
Model No. | DP-101ZL3-M-P | DP-102ZL3-M-P | DP-101ZL3-M-P-C | DP-102ZL3-M-P-C | |
Regulatory compliance and certification | CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations), UL/c-UL Certification Type of | ||||
Type of pressure | Gauge pressure | ||||
Rated pressure range | -100.0~+100.0kPa | -0.100~+1.000MPa | -100.0~+100.0kPa | -0.100~+1.000MPa | |
Set pressure range | -101.0~+101.0kPa | -0.101~+1.010MPa | -101.0~+101.0kPa | -0.101~+1.010MPa | |
Pressure withstandability | 500kPa | 1.5MPa | 500kPa | 1.5MPa | |
Applicable fluid | Non-corrosive gas | ||||
Supply voltage | 12 to 24 V DC ±10 % Ripple P-P 10 % or less | ||||
Power consumption (Note 2) | Normal operation: 720 mW or less (Current consumption 30 mA or less at 24 V supply voltage) ECO mode: 480 mW or less at STD (Current consumption 20 mA or less at 24 V supply voltage) 360 mW or less at FULL (Current consumption 15 mA or less at 24 V supply voltage) |
||||
Communication output (C/Q) (Note 3) |
IO-Link communication |
IO-Link Specification V1.1 | |||
Baud rate | COM3(230.4kbps) | ||||
Process data | 4byte | ||||
Minimum cycle time |
1.0ms | ||||
Control output (DO) | PNP open-collector transistor • Maximum source current: 50 mA • Applied voltage: 30 V DC or less (between output and +V) • Residual voltage: 2 V or less (at 50 mA source current) |
||||
Output operation | NO/NC (selectable by key operation) | ||||
Output modes | EASY mode / Hysteresis mode / Window comparator mode | ||||
Hysteresis | Minimum 1 digit (variable) | ||||
Repeatability | ±0.1%F.S.(within ±2 digits) | ±0.2%F.S.(within ±2 digits) | ±0.1%F.S(within ±2 digits) | ±0.2%F.S.(within ±2 digits) | |
Response time | 2.5ms、5ms、10ms、25ms、50ms、100ms、250ms、500ms、1,000ms、5,000ms selectable by key operation | ||||
Short-circuit protection | Incorporated | ||||
Display | 4 digits + 4 digits 3-color LCD display (Display refresh rate: 250 ms, 500 ms, 1,000 ms, selectable by key operation) | ||||
Displayable pressure range | -101.0~+101.0kPa | -0.101~+1.010MPa | -101.0~+101.0kPa | -0.101~+1.010MPa | |
Output indicator | Orange LED (Output operation indicator 1: Flashes during IO-Link communication, Lights up when the control output is ON during non-IO-Link communication (synchronized with the output operation indicator 2) Output operation indicator 2: Lights up when the control output is ON) |
||||
Environmental resistance | Protection | IP40(IEC) | |||
Ambient temperature | −10 to +50℃ +14 to +122 ℉(No dew condensation or icing allowed), Storage: −10 to +60℃ +14 to +140 ℉ | ||||
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH | ||||
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure | ||||
Insulation resistance | 50 MΩ or more with 500 V DC megger between all supply terminals connected together and enclosure | ||||
Vibration resistance | 10 to 500 Hz frequency, 3 mm 0.118 in double amplitude or maximum acceleration 196 m/s2, in X, Y and Z directions for two hours each (when panel or flat attachment is mounted: 10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude or maximum acceleration 49 m/s2, in X, Y and Z directions for two hours each) |
||||
Shock resistance | 100 m/s2 acceleration (10 G approx.) in X, Y and Z directions three times each | ||||
Temperature characteristics | Within ±0.5 % F.S. (at +20℃ +68 ℉) |
Within ±1 % F.S. (at +20℃ +68 ℉) |
Within ±0.5 % F.S. (at +20℃ +68 ℉) |
Within ±1 % F.S. (at +20℃ +68 ℉) |
|
Pressure port | M5 female thread | ||||
Material | Enclosure: PBT (glass fiber reinforced), LCD display: Acrylic, Pressure port: Stainless steel (SUS303) , Mounting threaded part: Brass (nickel plated), Switch part: Silicone rubber |
||||
Connecting method | Connector | ||||
Cable length | Total length up to 20 m 65.617 ft (Condition of CE compliance less than 20 m 65.617 ft) is possible with 0.3 mm2, or more, cable. | ||||
Weight | Net weight: 30 g approx., Gross weight: 125 g approx. | Net weight: 30 g approx., Gross weight: 95 g approx. | |||
Accessories | CN-14A-C2 (Connector attached cable 2 m 6.562 ft): 1 pc. | Dedicated M12 connector cable, 0.3 m 0.984 ft long: 1 pc. |
Notes: 1) | Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20℃ +68℉. |
---|---|
2) | The power consumption does not include the output load current. |
3) | When the sensor is used as an ordinary sensor, the communication output (C/Q) provides the same output operation as the control output (DO). |
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)