Business > Industrial Devices > Automation Controls Top > FA Sensors & Components > Pressure Sensors / Flow Sensors > Pressure Sensors / Flow Sensors > Head-separated Digital Pressure Sensor DP5/DPH(Discontinued Products) > Specifications
We are sorry, the products have been discontinued. Please refer to the details of the discontinued products and the recommended substitutes list below.
|
|
Type | Vacuum pressure | ||||
---|---|---|---|---|---|
-101 kPa type | |||||
Model No. | DPH-A00 | DPH-A10 | DPH-A20 | DPH-A30 | |
Type of pressure | Gauge pressure | ||||
Rated pressure range (Note 2) | 0 to -101.3 kPa | ||||
Pressure withstandability | 500 kPa | ||||
Applicable fluid | Non-corrosive gas | ||||
Supply voltage | 12 to 24 V DC +10/-15 % Ripple P-P 10 % or less | ||||
Current consumption | 15 mA or less (operation indicator lights off) / 17 mA or less (operation indicator lights on) | ||||
Analog voltage output | (Note 4) Output voltage: 1 to 5 V (over rated pressure range) Zero point: within 1 V ±2 % F.S. (vacuum / positive pressure type) within 3 V ±3 % F.S. (compound pressure type) Span: within 4 V ±3.5 % F.S. Linearity: within ±1 % F.S. Output impedance: 1 kΩ approx. Output current: 10 μA |
||||
Pollution degree | 3 (Industrial environment) | ||||
Protection | IP40 (IEC) | ||||
Ambient temperature | 0 to +50 ℃ +32 to +122 ℉ (No dew condensation), Storage: -10 to +60 ℃ +14 to +140 ℉ |
||||
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH | ||||
EMC | EN 61000-6-2, EN61000-6-4 | ||||
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure |
||||
Insulation resistance | 50 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure | ||||
Vibration resistance | 10 to 500 Hz frequency, 3 mm 0.118 in amplitude, in X, Y and Z directions for two hours each |
||||
Shock resistance | 1,000 m/s2 acceleration (100 G approx.) in X, Y and Z directions for three times each |
||||
Operation indicator | Orange LED [lights up when the Comparative Output 1 is ON (only in case of connection to the DP5 series pressure controller)] |
||||
Temperature characteristics | Over ambient temperature range +10 to +40 ℃ +50 to +104 ℉ : within ±1 % F.S. of detected pressure at +25 ℃ +77 ℉ Over ambient temperature range 0 to +50 ℃ +32 to +122 ℉ : within ±3 % F.S. of detected pressure at +25 ℃ +77 ℉ |
||||
Voltage characteristics | Within ±0.5 % F.S. for ±10 % fluctuation of the supply voltage | ||||
Pressure port | DPH-A0□: M5 male thread (for installing gasket), DPH-A1□: R (PT) 1/8 male thread / M5 female thread DPH-A2□: NPT 1/8 male thread / 10-32UNF female thread, DPH-A30: 10-32UNF male thread (for installing gasket) |
||||
Material | Enclosure: PBT, Pressure port: Brass (nickel plated) [however, stainless steel (SUS303) in case of DPH-A0□] |
||||
Connecting method | Connector | ||||
Cable | 0.2 mm2 4-core oil resistant cabtyre cable with connector, 100 mm 3.937 in long |
||||
Cable extension | Extension up to total 10 m 32.808 ft is possible with 0.3 mm2, or more, cable. |
||||
Net weight | DPH-A0□ / DPH-A30: 6 g approx., DPH-A1□ / DPH-A2□: 10 g approx. |
||||
Accessories | Gasket (DPH-A0□, DPH-A30 only) |
Type | Positive pressure | Compound pressure | |||||
---|---|---|---|---|---|---|---|
1 MPa type | ±100 kPa type | ||||||
Model No. | DPH-A02 | DPH-A12 | DPH-A22 | DPH-A07 | DPH-A17 | DPH-A27 | |
Type of pressure | Gauge pressure | ||||||
Rated pressure range (Note 2) | 0 to 1.000 MPa | -100.0 to 100.0 kPa | |||||
Pressure withstandability | 1.500 MPa | 500 kPa | |||||
Applicable fluid | Non-corrosive gas | ||||||
Supply voltage | 12 to 24 V DC +10/-15 % Ripple P-P 10 % or less | ||||||
Current consumption | 15 mA or less (operation indicator lights off) / 17 mA or less (operation indicator lights on) | ||||||
Analog voltage output | (Note 4) Output voltage: 1 to 5 V (over rated pressure range) Zero point: within 1 V ±2 % F.S. (vacuum / positive pressure type) within 3 V ±3 % F.S. (compound pressure type) Span: within 4 V ±3.5 % F.S. Linearity: within ±1 % F.S. Output impedance: 1 kΩ approx. Output current: 10 μA |
||||||
Pollution degree | 3 (Industrial environment) | ||||||
Protection | IP40 (IEC) | ||||||
Ambient temperature | 0 to +50 ℃ +32 to +122 ℉ (No dew condensation), Storage: -10 to +60 ℃ +14 to +140 ℉ |
||||||
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH | ||||||
EMC | EN 61000-6-2, EN61000-6-4 | ||||||
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure |
||||||
Insulation resistance | 50 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure | ||||||
Vibration resistance | 10 to 500 Hz frequency, 3 mm 0.118 in amplitude, in X, Y and Z directions for two hours each |
||||||
Shock resistance | 1,000 m/s2 acceleration (100 G approx.) in X, Y and Z directions for three times each |
||||||
Operation indicator | Orange LED [lights up when the Comparative Output 1 is ON (only in case of connection to the DP5 series pressure controller)] |
||||||
Temperature characteristics | Over ambient temperature range +10 to +40 ℃ +50 to +104 ℉ : within ±1 % F.S. of detected pressure at +25 ℃ +77 ℉ Over ambient temperature range 0 to +50 ℃ +32 to +122 ℉ : within ±3 % F.S. of detected pressure at +25 ℃ +77 ℉ |
||||||
Voltage characteristics | Within ±0.5 % F.S. for ±10 % fluctuation of the supply voltage | ||||||
Pressure port | DPH-A0□: M5 male thread (for installing gasket), DPH-A1□: R (PT) 1/8 male thread / M5 female thread DPH-A2□: NPT 1/8 male thread / 10-32UNF female thread |
||||||
Material | Enclosure: PBT, Pressure port: Brass (nickel plated) [however, stainless steel (SUS303) in case of DPH-A0□] |
||||||
Connecting method | Connector | ||||||
Cable | 0.2 mm2 4-core oil resistant cabtyre cable with connector, 100 mm 3.937 in long |
||||||
Cable extension | Extension up to total 10 m 32.808 ft is possible with 0.3 mm2, or more, cable. |
||||||
Net weight | DPH-A0□ / DPH-A30: 6 g approx., DPH-A1□ / DPH-A2□: 10 g approx. |
||||||
Accessories | Gasket (DPH-A0□ only) |
Notes:
1) Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20 ℃ +68 ℉.
2) The rated pressure range indicates the range for full product performance.
3) The sensor head can be used independently.
4) Analog voltage output
|
Type | NPN output type | PNP output type | |
---|---|---|---|
Model No. | DP5-C | DP5-C-P | |
Applicable sensor head | DPH-A00, DPH-A02, DPH-A07, DPH-A10, DPH-A12, DPH-A17, DPH-A20, DPH-A22, DPH-A27, DPH-A30 |
||
Rated pressure range (Note 2) | Vacuum pressure: 0 to -101.3 kPa, Positive pressure: 0 to 1.000 MPa, Compound pressure: -100.0 to 100.0 kPa |
||
Set pressure range (Note 2) | Vacuum pressure : 101.3 to -101.3 kPa (1.033 to -1.033 kgf/cm2, 14.70 to -14.70 psi, 1.013 to -1.013 bar, 760 to -760 mmHg, 29.9 to -29.9 inHg) Positive pressure : -1.050 to 1.050 MPa (-10.71 to 10.71 kgf/cm2, -152.2 to 152.2 psi, -10.50 to 10.50 bar) Compound pressure : -199.9 to 199.9 kPa (-1.999 to 1.999 kgf/cm2, -19.98 to 19.98 psi, -1.999 to 1.999 bar, -1510 to 1537 mmHg, -59.4 to 60.5 inHg) |
||
Supply voltage / Current consumption | 12 to 24 V DC +10/-15 % Ripple P-P 10 % or less / 60 mA or less (not including sensor head) |
||
Sensor supply voltage | Same as supply voltage | ||
Comparative outputs (Comparative Output 1, 2) |
NPN open-collector transistor (2 outputs) ・Maximum sink current: 100 mA ・Applied voltage: 30 V DC or less (between comparative output and 0 V) ・Residual voltage: 1 V or less (at 100 mA sink current) 0.4 V or less (at 16 mA sink current) |
PNP open-collector transistor (2 outputs) ・Maximum source current: 100 mA ・Applied voltage: Same as supply voltage (between comparative output and +V) ・Residual voltage: 2 V or less (at 100 mA source current) |
|
Utilization category | DC-12 or DC-13 | ||
Output operation | NO / NC, selectable by key operation | ||
Output modes | Equipped with 4 types of modes: hysteresis mode, window comparator mode, leak test mode, forced output mode (selectable by key operation) |
||
Hysteresis | 1 digit (however, variable in hysteresis mode, variable for Comparative Output 1 only when using leak test mode) |
||
Repeatability | With vacuum / positive pressure type sensor head : within ±0.2 % F.S. ±1 digit (±3 digits) With compound pressure type sensor head : within ±0.2 % F.S. ±2 digits (±6 digits) |
||
Response time | 1 ms, 16 ms, 128 ms, 512 ms or less, selectable by key operation (however, set response time is + 2 ms when auto-reference / remote zero-adjustment input is applied) |
||
Short-circuit protection | Incorporated | ||
Inputs | Sensor head input | Input voltage range: 1 to 5 V DC (over rated pressure range) | |
External input (Auto-reference / Remote zero-adjustment function) |
Input condition: NPN non-contact input [operates in Low (fall) state] Signal condition: High...5 to 30 V, or open Low....0.4 V or less Low level input time...2 ms or more |
Input condition: PNP non-contact input [operates in High (rise) state] Signal condition: High...5 to 30 V Low....0.4 V or less, or open High level input time...2 ms or more |
|
Analog voltage output | (Note 4) Output voltage: 1 to 5 V DC (over rated pressure range) Zero point: within 1 V ± 2.5 % F.S. (vacuum / positive pressure type) within 3 V ±3.5 % F.S. (compound pressure type) Span: within 4 V ±4 % F.S. Linearity: within ±1 % F.S. Output impedance: 1 kΩ approx. |
||
Display | 3 1/2 digit LCD display (with red and green backlight) (Display refresh rate: 256 ms, 512 ms or 1,024 ms selectable by key operation) |
||
Displayable pressure range |
Vacuum pressure: 5.1 to -101.3 kPa (0.052 to -1.033 kgf/cm2, 0.74 to -14.70 psi, 0.051 to -1.013 bar, 38 to -760 mmHg, 1.5 to -29.9 inHg) Positive pressure: -0.050 to 1.050 MPa (-0.51 to 10.71 kgf/cm2, -7.2 to 152.2 psi, -0.50 to 10.50 bar) Compound pressure: -101.3 to 105.0 kPa (-1.033 to 1.071 kgf/cm2, -14.70 to 15.22 psi, -1.013 to 1.050 bar, -760 to 787 mmHg, -29.9 to 31.0 inHg) |
||
Operation display | LCD segment is red when the comparative output is ON, and green when it is OFF (output is selected via supplementary settings) |
||
Analog bar display | Bar display in steps of 14 % F.S. approx. | ||
Operation indicator | Orange LED (lights up when the Comparative Output 1 is ON), Green LED (lights up when the Comparative Output 2 is ON) |
||
Pollution degree | 3 (Industrial environment) | ||
Protection | IP40 (IEC) | ||
Ambient temperature | 0 to +50 ℃ +32 to +122 ℉ (No dew condensation), Storage: -10 to +60 ℃ +14 to +140 ℉ |
||
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH | ||
EMC | EN 61000-6-2, EN 61000-6-4 | ||
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure |
||
Insulation resistance | 50 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure |
||
Vibration resistance | 10 to 150 Hz frequency, 0.75 mm 0.030 in amplitude, in X, Y and Z directions for two hours each |
||
Shock resistance | 100 m/s2 acceleration (10 G approx.) in X, Y and Z directions for three times each |
||
Temperature characteristics | Over ambient temperature range 0 to +50 ℃ +32 to +122 ℉ : within ±0.5 % F.S. of detected pressure at +25 ℃ +77 ℉ (not including sensor head) |
||
Material | Front case: ABS, LCD display section: PET, Rear case: PBT | ||
Connecting method | Connector | ||
Suitable cable | Conductor cross-section area | 0.16 to 0.32 mm2 (AWG#25 to #22) (Note 3) | |
Lead wire diameter | ø1.2 to ø1.8 mm ø0.047 to ø0.071 in | ||
Wire material | Tin plated, soft, twisted copper wire | ||
Cable length | Total length up to 100 m 328.084 ft (less than 10 m 32.808 ft when conforming to CE marking) is possible with 0.3 mm2, or more, cable. | ||
Weight | Net weight: 20 g approx. | ||
Accessories | Panel mounting bracket (MS-DP-1): 1 set, Connector: 1 set (Housing: 1 pc., Connector pin: 6 pcs.), Pressure unit label: 1 set., Connector cap: 1 pc. |
Notes:
1) Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20 ℃ +68 ℉.
2) The rated pressure range indicates the range for full product performance. It changes automatically according to the connected pressure sensor head.
3) If the wiring is longer than 5 m 16.404 ft, use a cable with a diameter of 0.3 mm2 or more.
4) Analog voltage output
|
|
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)