AUTOMATION
CONTROLS

Search
Discontinued
Products



Head-separated Digital Pressure Sensor DP5/DPH (Discontinued Products)

Specifications

Sensor head

Type Vacuum pressure
-101 kPa type
Model No. DPH-A00 DPH-A10 DPH-A20 DPH-A30
Type of pressure Gauge pressure
Rated pressure range (Note 2) 0 to -101.3 kPa
Pressure withstandability 500 kPa
Applicable fluid Non-corrosive gas
Supply voltage 12 to 24 V DC +10/-15 % Ripple P-P 10 % or less
Current consumption 15 mA or less (operation indicator lights off) / 17 mA or less (operation indicator lights on)
Analog voltage output (Note 4)

Output voltage: 1 to 5 V
(over rated pressure range)
Zero point: within 1 V ±2 % F.S. (vacuum / positive pressure type)
within 3 V ±3 % F.S.
(compound pressure type)
Span: within 4 V ±3.5 % F.S.
Linearity: within ±1 % F.S.
Output impedance: 1 kΩ approx.
Output current: 10 μA
Pollution degree 3 (Industrial environment)
Protection IP40 (IEC)
Ambient temperature 0 to +50 ℃ +32 to +122 ℉ (No dew condensation),
Storage: -10 to +60 ℃ +14 to +140 ℉
Ambient humidity 35 to 85 % RH, Storage: 35 to 85 % RH
EMC EN 61000-6-2, EN61000-6-4
Voltage withstandability 1,000 V AC for one min.
between all supply terminals connected together and enclosure
Insulation resistance 50 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure
Vibration resistance 10 to 500 Hz frequency, 3 mm 0.118 in amplitude,
in X, Y and Z directions for two hours each
Shock resistance 1,000 m/s2 acceleration (100 G approx.) in X, Y and Z directions
for three times each
Operation indicator Orange LED
[lights up when the Comparative Output 1 is ON
(only in case of connection to the DP5 series pressure controller)]
Temperature characteristics Over ambient temperature range +10 to +40 ℃ +50 to +104 ℉
: within ±1 % F.S. of detected pressure at +25 ℃ +77 ℉
Over ambient temperature range 0 to +50 ℃ +32 to +122 ℉
: within ±3 % F.S. of detected pressure at +25 ℃ +77 ℉
Voltage characteristics Within ±0.5 % F.S. for ±10 % fluctuation of the supply voltage
Pressure port DPH-A0□: M5 male thread (for installing gasket),
DPH-A1□: R (PT) 1/8 male thread / M5 female thread
DPH-A2□: NPT 1/8 male thread / 10-32UNF female thread,
DPH-A30: 10-32UNF male thread (for installing gasket)
Material Enclosure: PBT, Pressure port: Brass (nickel plated)
[however, stainless steel (SUS303) in case of DPH-A0□]
Connecting method Connector
Cable 0.2 mm2 4-core oil resistant cabtyre cable with connector,
100 mm 3.937 in long
Cable extension Extension up to total 10 m 32.808 ft is possible with 0.3 mm2,
or more, cable.
Net weight DPH-A0□ / DPH-A30: 6 g approx.,
DPH-A1□ / DPH-A2□: 10 g approx.
Accessories Gasket (DPH-A0□, DPH-A30 only)
Type Positive pressure Compound pressure
1 MPa type ±100 kPa type
Model No. DPH-A02 DPH-A12 DPH-A22 DPH-A07 DPH-A17 DPH-A27
Type of pressure Gauge pressure
Rated pressure range (Note 2) 0 to 1.000 MPa -100.0 to 100.0 kPa
Pressure withstandability 1.500 MPa 500 kPa
Applicable fluid Non-corrosive gas
Supply voltage 12 to 24 V DC +10/-15 % Ripple P-P 10 % or less
Current consumption 15 mA or less (operation indicator lights off) / 17 mA or less (operation indicator lights on)
Analog voltage output (Note 4)

Output voltage: 1 to 5 V
(over rated pressure range)
Zero point: within 1 V ±2 % F.S. (vacuum / positive pressure type)
within 3 V ±3 % F.S.
(compound pressure type)
Span: within 4 V ±3.5 % F.S.
Linearity: within ±1 % F.S.
Output impedance: 1 kΩ approx.
Output current: 10 μA
Pollution degree 3 (Industrial environment)
Protection IP40 (IEC)
Ambient temperature 0 to +50 ℃ +32 to +122 ℉ (No dew condensation),
Storage: -10 to +60 ℃ +14 to +140 ℉
Ambient humidity 35 to 85 % RH, Storage: 35 to 85 % RH
EMC EN 61000-6-2, EN61000-6-4
Voltage withstandability 1,000 V AC for one min.
between all supply terminals connected together and enclosure
Insulation resistance 50 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure
Vibration resistance 10 to 500 Hz frequency, 3 mm 0.118 in amplitude,
in X, Y and Z directions for two hours each
Shock resistance 1,000 m/s2 acceleration (100 G approx.) in X, Y and Z directions
for three times each
Operation indicator Orange LED
[lights up when the Comparative Output 1 is ON
(only in case of connection to the DP5 series pressure controller)]
Temperature characteristics Over ambient temperature range +10 to +40 ℃ +50 to +104 ℉
: within ±1 % F.S. of detected pressure at +25 ℃ +77 ℉
Over ambient temperature range 0 to +50 ℃ +32 to +122 ℉
: within ±3 % F.S. of detected pressure at +25 ℃ +77 ℉
Voltage characteristics Within ±0.5 % F.S. for ±10 % fluctuation of the supply voltage
Pressure port DPH-A0□: M5 male thread (for installing gasket),
DPH-A1□: R (PT) 1/8 male thread / M5 female thread
DPH-A2□: NPT 1/8 male thread / 10-32UNF female thread
Material Enclosure: PBT, Pressure port: Brass (nickel plated)
[however, stainless steel (SUS303) in case of DPH-A0□]
Connecting method Connector
Cable 0.2 mm2 4-core oil resistant cabtyre cable with connector,
100 mm 3.937 in long
Cable extension Extension up to total 10 m 32.808 ft is possible with 0.3 mm2,
or more, cable.
Net weight DPH-A0□ / DPH-A30: 6 g approx.,
DPH-A1□ / DPH-A2□: 10 g approx.
Accessories Gasket (DPH-A0□ only)

Notes:
1) Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20 ℃ +68 .
2) The rated pressure range indicates the range for full product performance.
3) The sensor head can be used independently.
4) Analog voltage output

Controller

Type NPN output type PNP output type
Model No. DP5-C DP5-C-P
Applicable sensor head DPH-A00, DPH-A02, DPH-A07, DPH-A10, DPH-A12,
DPH-A17, DPH-A20, DPH-A22, DPH-A27, DPH-A30
Rated pressure range (Note 2) Vacuum pressure: 0 to -101.3 kPa,
Positive pressure: 0 to 1.000 MPa,
Compound pressure: -100.0 to 100.0 kPa
Set pressure range (Note 2) Vacuum pressure : 101.3 to -101.3 kPa
(1.033 to -1.033 kgf/cm2, 14.70 to -14.70 psi, 1.013 to -1.013 bar, 760 to -760 mmHg, 29.9 to -29.9 inHg)
Positive pressure : -1.050 to 1.050 MPa
(-10.71 to 10.71 kgf/cm2, -152.2 to 152.2 psi, -10.50 to 10.50 bar)
Compound pressure : -199.9 to 199.9 kPa
(-1.999 to 1.999 kgf/cm2, -19.98 to 19.98 psi, -1.999 to 1.999 bar, -1510 to 1537 mmHg, -59.4 to 60.5 inHg)
Supply voltage / Current consumption 12 to 24 V DC +10/-15 % Ripple P-P 10 % or less
/ 60 mA or less (not including sensor head)
Sensor supply voltage Same as supply voltage
Comparative outputs
(Comparative Output 1, 2)
NPN open-collector transistor (2 outputs)
・Maximum sink current: 100 mA
・Applied voltage: 30 V DC or less
(between comparative output and 0 V)
・Residual voltage: 1 V or less (at 100 mA sink current)
0.4 V or less (at 16 mA sink current)
PNP open-collector transistor (2 outputs)
・Maximum source current: 100 mA
・Applied voltage: Same as supply voltage
(between comparative output and +V)
・Residual voltage: 2 V or less (at 100 mA source current)
  Utilization category DC-12 or DC-13
Output operation NO / NC, selectable by key operation
Output modes Equipped with 4 types of modes: hysteresis mode,
window comparator mode, leak test mode,
forced output mode (selectable by key operation)
Hysteresis 1 digit (however, variable in hysteresis mode,
variable for Comparative Output 1 only when using leak test mode)
Repeatability With vacuum / positive pressure type sensor head
: within ±0.2 % F.S. ±1 digit (±3 digits)
With compound pressure type sensor head
: within ±0.2 % F.S. ±2 digits (±6 digits)
Response time 1 ms, 16 ms, 128 ms, 512 ms or less, selectable by key operation
(however, set response time is + 2 ms when auto-reference
/ remote zero-adjustment input is applied)
Short-circuit protection Incorporated
Inputs Sensor head input Input voltage range: 1 to 5 V DC (over rated pressure range)
External input
(Auto-reference / Remote
zero-adjustment function)
Input condition: NPN non-contact input
[operates in Low (fall) state]
Signal condition: High...5 to 30 V, or open
Low....0.4 V or less
Low level input time...2 ms or more
Input condition: PNP non-contact input
[operates in High (rise) state]
Signal condition: High...5 to 30 V
Low....0.4 V or less, or open
High level input time...2 ms or more
Analog voltage output (Note 4)

Output voltage: 1 to 5 V DC (over rated pressure range)
Zero point: within 1 V ± 2.5 % F.S.
(vacuum / positive pressure type)
within 3 V ±3.5 % F.S. (compound pressure type)
Span: within 4 V ±4 % F.S.
Linearity: within ±1 % F.S.
Output impedance: 1 kΩ approx.
Display 3 1/2 digit LCD display (with red and green backlight)
(Display refresh rate: 256 ms, 512 ms or 1,024 ms selectable by key operation)
  Displayable pressure
range
Vacuum pressure: 5.1 to -101.3 kPa
(0.052 to -1.033 kgf/cm2, 0.74 to -14.70 psi, 0.051 to -1.013 bar, 38 to -760 mmHg, 1.5 to -29.9 inHg)
Positive pressure: -0.050 to 1.050 MPa
(-0.51 to 10.71 kgf/cm2, -7.2 to 152.2 psi, -0.50 to 10.50 bar)
Compound pressure: -101.3 to 105.0 kPa
(-1.033 to 1.071 kgf/cm2, -14.70 to 15.22 psi, -1.013 to 1.050 bar, -760 to 787 mmHg, -29.9 to 31.0 inHg)
Operation display LCD segment is red when the comparative output is ON,
and green when it is OFF (output is selected via supplementary settings)
Analog bar display Bar display in steps of 14 % F.S. approx.
Operation indicator Orange LED (lights up when the Comparative Output 1 is ON),
Green LED (lights up when the Comparative Output 2 is ON)
Pollution degree 3 (Industrial environment)
Protection IP40 (IEC)
Ambient temperature 0 to +50 ℃ +32 to +122 ℉ (No dew condensation),
Storage: -10 to +60 ℃ +14 to +140 ℉
Ambient humidity 35 to 85 % RH, Storage: 35 to 85 % RH
EMC EN 61000-6-2, EN 61000-6-4
Voltage withstandability 1,000 V AC for one min.
between all supply terminals connected together and enclosure
Insulation resistance 50 MΩ, or more, with 500 V DC megger
between all supply terminals connected together and enclosure
Vibration resistance 10 to 150 Hz frequency, 0.75 mm 0.030 in amplitude,
in X, Y and Z directions for two hours each
Shock resistance 100 m/s2 acceleration (10 G approx.) in
X, Y and Z directions for three times each
Temperature characteristics Over ambient temperature range 0 to +50 ℃ +32 to +122 ℉
: within ±0.5 % F.S. of detected pressure at +25 ℃ +77 ℉
(not including sensor head)
Material Front case: ABS, LCD display section: PET, Rear case: PBT
Connecting method Connector
Suitable cable Conductor cross-section area 0.16 to 0.32 mm2 (AWG#25 to #22) (Note 3)
Lead wire diameter ø1.2 to ø1.8 mm ø0.047 to ø0.071 in
Wire material Tin plated, soft, twisted copper wire
Cable length Total length up to 100 m 328.084 ft (less than 10 m 32.808 ft when conforming to CE marking) is possible with 0.3 mm2, or more, cable.
Weight Net weight: 20 g approx.
Accessories Panel mounting bracket (MS-DP-1): 1 set,
Connector: 1 set (Housing: 1 pc., Connector pin: 6 pcs.),
Pressure unit label: 1 set.,
Connector cap: 1 pc.

Notes:
1) Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20 ℃ +68 .
2) The rated pressure range indicates the range for full product performance. It changes automatically according to the connected pressure sensor head.
3) If the wiring is longer than 5 m 16.404 ft, use a cable with a diameter of 0.3 mm2 or more.
4) Analog voltage output

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region




Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)