I/O Circuit and Wiring diagrams

NPN output type

I/O circuit diagram
Controller / TH-C1, TH-C2

I/O circuit diagram
Note: The external synchronization input is active Low.

*1

Specifying channel with external channel select inputs

Channel No. EXT.1 (Orange) EXT.2 (Pink) EXT.3 (Violet)
1 L H H
2 H L H
3 L L H
4 H H L
5 L H L
6 H L L
7 L L L
8 H H H

L: Low (0 to 1 V), H: High (4.5 to 30 V, or open)

Notes:

1) The channel can be specified from the front panel only when all external channel select inputs (EXT.1, EXT.2, and EXT.3) are High (corresponding to Channel No. 8).
2) The external channel select inputs take precedence over the front panel channel selection (except for Channel No. 8).
3) If channel specification is changed from front panel operation to external channel select inputs and Channel No. 8 is to be selected by the external channel call inputs, make sure to specify a channel other than No. 8 before setting all the external channel select inputs (EXT.1, EXT.2, EXT.3) to High.
If this operation is not done, channel specification by front panel operation gets precedence.

PNP output type

I/O circuit diagram
Controller / TH-C2P

I/O circuit diagram
Note: The external synchronization input is active High.

*1

*2

Specifying channel with external channel select inputs

Channel No. EXT.1 (Orange) EXT.2 (Pink) EXT.3 (Violet)
1 L H H
2 H L H
3 L L H
4 H H L
5 L H L
6 H L L
7 L L L
8 H H H

L: Low (0 to 1 V), H: High (4.5 to 30 V, or open)

Notes:

1) The channel can be specified from the front panel only when all external channel select inputs (EXT.1, EXT.2, and EXT.3) are High (corresponding to Channel No. 8).
2) The external channel select inputs take precedence over the front panel channel selection (except for Channel No. 8).
3) If channel specification is changed from front panel operation to external channel select inputs and Channel No. 8 is to be selected by the external channel call inputs, make sure to specify a channel other than No. 8 before setting all the external channel select inputs (EXT.1, EXT.2, EXT.3) to High.
If this operation is not done, channel specification by front panel operation gets precedence.

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region




Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)