AUTOMATION
CONTROLS

Search
Discontinued
Products



Pipe-mountable Liquid Level Detection Sensor EX-F1

Specifications

Type Amplifier built-in, Pipe-mountable
Model No. EX-F1
CE marking directive compliance EMC Directive, RoHS Directive
Sensing object Liquid (Note 2)
Applicable pipe diameter Outer dia. ø6 to ø13 mm ø0.236 to ø0.512 in transparent resin pipe
[PFA (Fluorine resin) or equivalently transparent pipe, wall thickness 1 mm 0.039 in ] (Note 3)
Supply voltage / Current consumption 12 to 24 V DC ± 10 % Ripple P-P 10 % or less / 30 mA or less
Output NPN open-collector transistor
- Maximum sink current: 100 mA
- Applied voltage: 30 V DC or less (between output and 0 V)
- Residual voltage: 1 V or less (at 100 mA sink current)
0.4 V or less (at 16 mA sink current)
  Utilization category DC-12 or DC-13
Output operation Switchable either Light-ON (Liquid-absent-ON) or Dark-ON (Liquid-present-ON)
Short-circuit protection Incorporated
Response time 2 ms or less
Operation indicator Red LED (lights up when the output is ON)
Pollution degree 3 (Industrial environment)
Ambient temperature (Note 4) -10 to +55 ℃ +14 to +131 ℉ (No dew condensation or icing allowed), Storage: -20 to +70 ℃ -4 to +158 ℉
Ambient humidity / Ambient illuminance 35 to 85 % RH, Storage: 35 to 85 % RH / lncandescent light: 3,000 lx or less at the light-receiving face
Voltage withstandability 1,000 V AC for one min. between all supply terminals connected together and enclosure
Insulation resistance 20 MΩ, or more, with 250 V DC megger between all supply terminals connected together and enclosure
Vibration resistance 10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
Shock resistance 100 m/s2 acceleration (10 G approx.) in X, Y and Z directions three times each
Emitting element Infrared LED (modulated)
Material Enclosure: Polycarbonate, Tying band: Nylon, Anti-slip tube: Silicone
Cable 0.1 mm2 3-core cabtyre cable, 1 m 3.281 ft long
Cable extension Extension up to total 50 m 164.042 ft is possible with 0.3 mm2, or more, cable.
Weight Net weight: 15 g approx., Gross weight: 60 g approx.
Accessories Tying band: 2 pcs., Anti-slip tube: 2 pcs.

Note 1:Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20 ℃ +68 ℉.
Note 2:Unclear or highly viscous liquid may not be detected stably.
Note 3:Do not use the sensor with pipes other than the above specified.
Note 4:Liquid being detected should also be kept within the rated ambient temperature range.

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region




Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)