AUTOMATION
CONTROLS

Search
Discontinued
Products



S-LINK V gateway controller for open network

Cautions For Use

Version upgrade of SL-VGU1-EC

The version of SL-VGU1-EC and the version of ESI file have been changed.

  Production before December 2020 Production after January 2021
Software version Ver. 1.00 Ver. 1.10
ESI file version Ver. 1.00 Ver. 1.10
Use on the same network Yes
Display on the tool SL-VGU1-EC
Rev:0X00000001
SL-VGU1-EC
Rev:0X00000002
Product nameplate
(changed part: red frame)

No version notation

Version Ver1.1 notation

Combination of old and new versions

SL-VGU1-EC Ver1.10(New) Ver1.10(New) Ver1.00(Old)
ESI file Ver1.10(New) Ver1.00(Old) Ver1.10(New)
Slave recognition SL-VGU1-EC
Rev:0x00000002
Unrecognizable(Note) SL-VGU1-EC
Rev:0x00000001
PDO communication Normal operation (Note 1) Normal operation
SDO communication Normal operation (Note 1) Normal operation
(Note 1) : When the slave information is updated, the old ESI file does not have the SL-VGU1-EC Ver.1.10 information, and the slave becomes an unknown slave.
Please rebuild the system network information with ESI file Ver1.10.

Notes

■When SL-VGU1-EC is replaced with Ver1.10 for maintenance
Please rebuild the system network information with ESI file Ver1.10.

* The ESI file Ver.1.10 can be downloaded from the website.
* To download the file, you need to register as a web member on the Panasonic Automation Control English (Global) website.
>>Click here to download the ESI file for SL-VGU1-EC

 

■How to use ESI file Ver1.10
ESI file Ver1.10 is compatible with the new / old version of SL-VGU1-EC.
Normally, it is automatically recognized, but if you want to set it manually, select as follows according to the version of SL-VGU1-EC.
・Old SL-VGU1-EC(Ver1.00) : Rev:0x00000001
・New SL-VGU1-EC(Ver1.10) : Rev:0x00000002

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region




Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)