AUTOMATION
CONTROLS

Search
Discontinued
Products



S-LINK V gateway controller for open network

Specifications

SL-VGU1-EC

Designation S-LINK V gateway controller for EtherCAT
Model No. SL-VGU1-EC
Supply voltage 24 V DC+10–5%
Current consumption 300 mA or less
(excluding error output load and power supply for driving I/O units) (Note 1)
Allowable through current 7A (Note 2)
S-LINK V
side
Transmission speed A mode: 110 kbps, B mode: 27.5 kbps, C mode: 6.9 kbps
Refresh time A mode: 0.29 to 10.32 ms, B mode: 1.18 to 41.29 ms,
C mode: 4.70 to 165.15 ms
I/O points Max. 512 points
Connected node No. Max. 256 nodes
Transmission distance A mode: 50 m 164 ft max., B mode: 200 m 656 ft max., C mode: 800 m 2,625 ft max.
Total wiring length A mode: 100 m 328 ft or less, B mode: 400 m 1,312 ft or less, C mode: 1,600 m 5,249 ft or less
Transmission cable Exclusive 4-core flat cable (0.5 mm2) or conductor cross-section area
0.3 to 2.0 mm2 4-core VCTF cable (without shield) (Note 3)
I/O combination I/O settable in increments of 32 points
Error output NPN open-collector transistor
EtherCAT
communication
side
Protocol CoE PDO communication, SDO communication
Compliance IEEE802.3u (100BASE-TX)
Transmission speed 100 Mbps (100BASE-TX)
Transmission connector RJ-45 × 2
Distance between nodes 100 m 328 ft or less
Max. number of
station connections
4,095 stations (65,535 stations when set from master side)
Transmission cable Category 5e or more
Ambient temperature 0 to +55 ℃ +32 to +131 ℉ (No dew condensation),
Storage: -20 to +70 ℃ -4 to +158 ℉
Ambient humidity 10 to 90 % RH, Storage: 10 to 90 % RH
Material Enclosure: ABS
Weight 140 g approx.

Notes:

1) The current consumption value shown here is the total of the maximum current (D-G line only) supplied to the S-LINK V I/O units and the current consumption of the S-LINK V gateway controller.
2) This product is not equipped with any short-circuit protective function. For this reason, select a power supply unit having short-circuit protective function (fuse, etc.).
3) The VCTF cable is the vinyl cabtyre cable that conforms to the requirements of JIS C 3306 "Polyvinyl chloride insulated flexible cords."
4) In case connecting to commercially offered product, be sure to check with this product. Station No., transmission distance, transmission speed depend on the connected product.

Return to top

SL-VGU1-C

Designation S-LINK V gateway controller for CC-Link
Model No. SL-VGU1-C
Supply voltage 24V DC +10-5 %
Current consumption 300mA or less (excluding error output load and power supply for driving I/O units) (Note 2)
Allowable through current 7A (Note 3)
S-LINK V
system
side
Transmission speed A mode: 110kbps, B mode: 27.5kbps, C mode: 6.9kbps
Refresh time A mode: 0.29 to 10.32ms, B mode: 1.18 to 41.29ms, C mode: 4.70 to 165.15ms
I/O points Buffer memory assignment pattern 1:
128 inputs max., 128 outputs max. (Note 4)
Buffer memory assignment pattern 2:
256 inputs max., 256 outputs max. (Note 5)
Connected node No. 256 nodes max.
Transmission distance A mode: 50m max., B mode: 200m max., C mode: 800m max.
Total wiring length A mode: 100m or less, B mode: 400m or less, C mode: 1,600m or less
Transmission
cable
Exclusive 4-core flat cable (0.5mm2) or Conductor cross-section area 0.3 to 2.0mm2 4-core VCTF cable (without shield) (Note 6)
I/O combination I/O settable in units of 32 Nos.
Error output NPN open-collector transistor
CC-Link
side
Compatible network CC-Link Ver.1.10
Occupied station No. 1 to 4 stations (varies with S-LINK V I/O control points.)
Transmission speed 10Mbps 5Mbps 2.5Mbps 625kbps 156kbps
Total extension 100m 160m 400m 900m 1,200m
Transmission cable Specified cable (shielded twisted pair cable)
Remote unit
claccification
Remote device unit
Ambient temperature 0 to +55℃ (No dew condensation), Storage: -20 to +70℃
Ambient humidity 10 to 90% RH, Storage: 10 to 90% RH
Material Enclosure: ABS
Weight Approx. 200g

Notes:

1) Mainly the S-LINK Vsystem side specifications are given above. The CC-Link side conforms to CC-Link specifications. Please confirm the details from CC-Link Partner Association.
2) The current consumption value shown here is the total of the maximum current (D-G line only) supplied to the S-LINK V I/O units and the current consumption of the S-LINK V gateway controller.
3) This product is not equipped with any short-circuit protective function. For this reason, select a power supply unit having short-circuit protective function (fuse, etc.).
4) In case of buffer memory assignment pattern 1, 112 channels are assigned to remote I/O (RX / RY) and the balance 16 channels are assigned to remote register (RWrm / RWwm).
5) If buffer memory assignment pattern 2 is used, all the points will be assigned to the remote registers (RWrm / RWwm).
6) The VCTF cable is the vinyl cabtyre cable that conforms to the requirements of JIS C 3306 "Polyvinyl chloride insulated flexible cords."

Return to top

SL-VGU1-D

Designation S-LINK V gateway controller for DeviceNet
Model No. SL-VGU1-D
Supply voltage 24V DC +10-5 %
Current consumption 300mA or less (excluding error output load and power supply
for driving I/O units) (Note 2)
Allowable through current 7A (Note 3)
S-LINK V
system
side
Transmission speed A mode: 110kbps, B mode: 27.5kbps, C mode: 6.9kbps
Refresh time A mode: 0.29 to 10.32ms, B mode: 1.18 to 41.29ms
C mode: 4.70 to 165.15ms
I/O points 512 points max.
Connected node No. 256 nodes max.
Transmission distance A mode: 50m max., B mode: 200m max., C mode: 800m max.
Total wiring length A mode: 100m or less, B mode: 400m or less, C mode: 1,600m or less
Transmission
cable
Exclusive 4-core flat cable(0.5mm2) or Conductor cross-section area 0.3 to 2.0mm2 4-core VCTF cable (without shield) (Note 4)
I/O combination I/O settable in units of 32 Nos.
Error output NPN open-collector transistor
DeviceNet
side
Compatible network DeviceNet Specifications Release 2.0
Transmission
protocol
Poll, Change of State, Cyclic
Address setting 0 to 63 (set by address setting switch)
Transmission speed 500kbps 250kbps 125kbps
Total extension 100m 250m 500m
Transmission cable Exclusive DeviceNet cable
Ambient temperature 0 to +55℃ (No dew condensation), Storage: -20 to +70℃
Ambient humidity 10 to 90% RH, Storage: 10 to 90% RH
Material Enclosure: ABS
Weight Approx. 200g

Notes:

1) Mainly the S-LINK Vsystem side specifications are given above. The DeviceNet side conforms to DeviceNet specifications. Please confirm the details from ODVA (Open DeviceNet Vendor Association).
2) The current consumption value shown here is the total of the maximum current (D-G line only) supplied to the S-LINK V I/O units and the current consumption of the S-LINK V gateway controller.
3) This product is not equipped with any short-circuit protective function. For this reason, select a power supply unit having short-circuit protective function (fuse, etc.).
4) The VCTF cable is the vinyl cabtyre cable that conforms to the requirements of JIS C 3306 "Polyvinyl chloride insulated flexible cords."
5) EDS file is required before using this product.

Return to top

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region




Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)