Business > Industrial Devices > Automation Controls Top > FA Sensors & Components > Motors for FA & Industrial Application > AC Servo > MINAS E Series > System Configuration
Discontinuation plan
|
|
Power supply |
Motor | Power capacity (at rated output ) |
Circuit Breaker (Rated current) |
Noise Filter | Magnetic Contactor (Contact Composition) | Wire diameter (L1,L2,L3,U,V and W) |
|
---|---|---|---|---|---|---|---|
Series | Output | ||||||
Single phase, 100 V |
MUMA | 50 W | 0.3 kVA | 5 A | DV0P4160 | 10 A (3P+1a) |
0.75 mm2 to 0.85 mm2 AWG18 |
100 W | 0.4 kVA | ||||||
200 W | 0.5 kVA | 10 A | |||||
Single phase, 200 V |
50 W | 0.3 kVA | 5 A | 15 A (3P+1a) |
|||
100 W | |||||||
200 W | 0.5 kVA | ||||||
400 W | 0.9 kVA | 10 A | |||||
3-phase 200 V |
50 W | 0.3 kVA | 5 A | 10 A (3P+1a) |
|||
100 W | |||||||
200 W | 0.5 kVA | ||||||
400 W | 0.9 kVA | 10 A |
* Select the single and 3-phase common specifications corresponding to the power supplies.
To conform to EC Directives, install a circuit breaker which conforms to IEC and UL Standards (Listed, marked) between noise filter and power supply.
Remarks
• Use a copper conductor cables with temperature rating of 60 °C or higher for main power connector and ground terminal wiring.
• Use a cable for ground with diameter of 2.0 mm2 (AWG14) or larger.
|
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)