AUTOMATION
CONTROLS

Search
Discontinued
Products



MINAS E Series

System Configuration

Wiring of main circuit

 

List of recommended peripheral devices

Power
supply
Motor Power
capacity (at rated
output )
Circuit Breaker
(Rated current)
Noise Filter Magnetic Contactor (Contact Composition) Wire diameter
(L1,L2,L3,U,V and W)
Series Output
Single
phase,
100 V
MUMA 50 W 0.3 kVA 5 A DV0P4160 10 A
(3P+1a)
0.75 mm2 to 0.85 mm2
AWG18
100 W 0.4 kVA
200 W 0.5 kVA 10 A
Single
phase,
200 V
50 W 0.3 kVA 5 A 15 A
(3P+1a)
100 W
200 W 0.5 kVA
400 W 0.9 kVA 10 A
3-phase
200 V
50 W 0.3 kVA 5 A 10 A
(3P+1a)
100 W
200 W 0.5 kVA
400 W 0.9 kVA 10 A

* Select the single and 3-phase common specifications corresponding to the power supplies.


To conform to EC Directives, install a circuit breaker which conforms to IEC and UL Standards (Listed, marked) between noise filter and power supply.

Remarks
• Use a copper conductor cables with temperature rating of 60 °C or higher for main power connector and ground terminal wiring.
• Use a cable for ground with diameter of 2.0 mm2 (AWG14) or larger.

 