EX-F1 | Pipe-mountable Liquid Level Detection Sensor EX-F1


Pipe-mountable Liquid Level Detection Sensor EX-F1

*Photo may vary from actual product.

  • RoHS Compliant This product has been confirmed that it does not contain the 6 substances specified in EU RoHS Directive 2011/65/EU and the 4 substances specified in 2015/863/EU.  


Product Number EX-F1
Part Number EX-F1
Product Pipe-mountable Liquid Level Detection Sensor
Details Amplifier built-in, Pipe-mountable
Product name Pipe-mountable Liquid Level Detection Sensor EX-F1

As of May 18, 2024
Specifications and design of the products are subject to change without notice for the product improvement.

Spec Detail

Item Specifications
Product Number EX-F1
Part Number EX-F1
Regulatory compliance EMC Directive, RoHS Directive
Sensing object Liquid
(Note):Unclear or highly viscous liquid may not be detected stably.
Applicable pipe diameter Outer dia. ø6 to ø13 mm ø0.236 to ø0.512 in transparent resin pipe
[PFA (Fluorine resin) or equivalently transparent pipe, wall thickness 1 mm 0.039 in ]
(Note:Do not use the sensor with pipes other than the above specified.)
Supply voltage 12 to 24 V DC ± 10 % Ripple P-P 10 % or less
Current consumption 30 mA or less
(Note:Unclear or highly viscous liquid may not be detected stably.)
Output NPN open-collector transistor
- Maximum sink current: 100 mA
- Applied voltage: 30 V DC or less (between output and 0 V)
- Residual voltage: 1 V or less (at 100 mA sink current), 0.4 V or less (at 16 mA sink current)
Output:Output operation Switchable either Light-ON (Liquid-absent-ON) or Dark-ON (Liquid-present-ON)
Output:Short-circuit protection Incorporated
Response time 2 ms or less
Operation indicator Red LED (lights up when the output is ON)
Ambient temperature -10 to +55 ℃ +14 to +131 ℉ (No dew condensation or icing allowed), Storage: -20 to +70 ℃ -4 to +158 ℉
(Note:Liquid being detected should also be kept within the rated ambient temperature range.)
Ambient humidity 35 to 85 % RH, Storage: 35 to 85 % RH
Ambient illuminance lncandescent light: 3,000 lx or less at the light-receiving face
Voltage withstandability 1,000 V AC for one min. between all supply terminals connected together and enclosure
Insulation resistance 20 MΩ, or more, with 250 V DC megger between all supply terminals connected together and enclosure
Vibration resistance 10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
Shock resistance 100 m/s2 acceleration (10 G approx.) in X, Y and Z directions three times each
Emitting element Infrared LED (modulated)
Material Enclosure: Polycarbonate, Tying band: Nylon, Anti-slip tube: Silicone
Cable 0.1 mm2 3-core cabtyre cable, 1 m 3.281 ft long
Cable extension Extension up to total 50 m 164.042 ft is possible with 0.3 mm2, or more, cable.
Weight Net weight: 15 g approx., Gross weight: 60 g approx.
Accessory Tying band: 2 pcs., Anti-slip tube: 2 pcs.

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region



Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)