【Notification of Manufacturer Change for Panasonic Industrial Devices SUNX Products and Panasonic Industrial Devices SUNX Tatsuno Products】
From April 1, 2024, the terms "Panasonic Industrial Devices SUNX Co., Ltd." and "Panasonic Industrial Devices SUNX Tatsuno Co., Ltd."
in this page and in the manuals and other documents to be downloaded will all be replaced with "Panasonic Industry Co., Ltd." and applied accordingly.
Business > Industrial Devices > Automation Controls Top > FA Sensors & Components > Timers / Counters / FA Componets > Counters > LC4H-S Electronic Counters (with pre-scale function)(Discontinued Products) > Rating/ Performance
We are sorry, the products have been discontinued. Please refer to the details of the discontinued products and the recommended substitutes list below.
|
|
Type | Ralay output type | Transistor output type | |||
---|---|---|---|---|---|
Item | AC type | DC/AC type | DC/AC type | ||
Rating | Rated operating voltage | 100 to 240 V | 12 to 24 V DC/24 V AC | 12 to 24 V DC/24 V AC | |
Rated frequency | 50/60 Hz common | ||||
Rated power consumption | Max. 10 V A | Max. 3 W | |||
Rated control capacity | 5 A 250 V AC (resistive load) | 100 mA, 30 V DC | |||
Input mode | Addition (UP)/Subtraction (DOWN)/Direction (DIR)/Individuality (IND)/Phase (PHASE) 5 modes selectable by DIP switches |
||||
Max. counting speed | 30 Hz, 5 kHz (selectable by DIP switches) | ||||
Counting input (input 1, input 2) |
16.7 ms at 30 Hz/0.1 ms at 5 kHz ON time: OFF time = 1:1 | ||||
Reset input | Min. input signal width: 1 ms, 20 ms (selected by DIP switches) | ||||
Lock input | Min. input signal width: 20 ms | ||||
Input signal | Contact, Open collector input/DC two-wire system sensor Input impedance: 1 kΩ or less, Input residual voltage: 2 V or less, Open impedance: 100 kΩ or less, Max. energized voltage: 40 V DC |
||||
Output mode | HOLD-A, HOLD-B, HOLD-C, SHOT-A, SHOT-B, SHOT-C, SHOT-D, 7 modes selectable by DIP switches | ||||
One shot output time | 1 s, 0.5s, 0.2s, 0.1s, 0.05, 0.01s | ||||
Indication | 7-segment LCD, Counter value (backlight red LED), Setting value (backlight yellow LED) | ||||
Digit | 4-digit display type --999 to 9999 (0 to 9999 for setting) 6-digit display type --99999 to 999999 (0 to 999999 for setting) |
||||
Decimal point | Can be set to three digits | ||||
Pre-scaling | 0.001 to 9.999 (4-digit type), 0.001 to 99.999 (6-digit type) | ||||
Memory | EEP-ROM (Overwriting times: 105 ope. or more) | ||||
Power for senser | 12 V DC (±10%) 100 mA Max. | - | |||
Contact | Contact arrangement | 1 Form C | 1 Form A (Open collector) | ||
Initial contact resistance | 100 mΩ (at 1 A 6 V DC) | - | |||
Contact material | Ag alloy/Au flush | - | |||
Life | Mechanical (contact) |
2×107 ope. (Except for switch operation parts) | - | ||
Electrical (contact) |
105 ope. (At rated control voltage) | 107 ope. (At rated control voltage) | |||
Electrical | Operating voltage range | 85 to 264 V AC | 10.8 to 26.4 V DC, 20.4 to 26.4 V AC | ||
Initial withstand voltage | Between live and dead metal parts: 2,000 Vrms for 1 min (pin type) Between input and output: 2,000 Vrms for 1 min |
||||
Initial insulation resistance (At 500 V DC) |
Between live and dead metal parts: Min. 100 MΩ (pin type) Between input and output: Min. 100 MΩ |
||||
Temperature rise | Max. 65°C (under the flow of nominal operating current at nominal voltage) | ||||
Mechanical | Vibration resistance |
Functional | 10 to 55 Hz (1 cycle/min), single amplitude: 0.35 mm (10 min on 3 axes) | ||
Destructive | 10 to 55 Hz (1 cycle/min), single amplitude: 0.75 mm (1 h on 3 axes) | ||||
Shock resistance |
Functional | Min. 98 m/s2 (4 times on 3 axes) | |||
Destructive | Min. 294 m/s2 (5 times on 3 axes) | ||||
Operating conditions | Ambient temperature | --10°C to 55°C/ +14°F to +131°F | |||
Ambient humidity | Max. 85 % RH (non-condensing) | ||||
Air pressure | 860 to 1,060 h Pa | ||||
Connection | 11-pin/screw terminal | ||||
Protective construction | IP66 (front panel with a rubber gasket) |
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)