Rating/ Performance

Performance outline

Item Specifications
CE marking directive compliance Low Voltage Directive, EMC Directive, RoHS Directive
Size 48×96mm 1.890 × 3.780 in
Rating Rating power supply 100 - 240V AC
Rating frequency 50 / 60Hz
Rating power consumption 8 VA approx.
Rating
scale
Input type Input range
Thermocouple K -200 to 1,370℃ (-328 to 2,489℉)
-200.0 to 400.0℃ (-328.0 to 752.0℉)
J -200 to 1,000℃ (-328 to 1,832℉)
R 0 to 1,760℃ (0 to 3,200℉)
S 0 to 1,760℃ (0 to 3,200℉)
B 0 to 1,820℃ (32 to 3,308℉)
E -200 to 800℃ (-328 to 1,472℉)
T -200.0 to 400.0℃ (-328.0 to 752.0℉)
N -200 to 1,300℃ (-328 to 2,372℉)
PL-II 0 to 1,390℃ (32 to 2,534℉)
C
(W / Re5−26)
0 to 2,315℃ (32 to 4,199℉)
RTD Pt100 -200 to 850℃ (-328 to 1,562℉)
-200.0 to 850.0℃ (-328.0 to 1,562.0℉)
JPt100 -200 to 500℃ (-328 to 932℉)
-200 to 500.0℃ (-328.0 to 932.0℉)
DC Current 4 to 20 mA DC -2,000 to 10,000
0 to 20 mA DC
Voltage 0 to 1 V DC
0 to 10 V DC
1 to 5 V DC
0 to 5 V DC
  ・Scaling and change to the decimal point position is possible for DC current input and DC voltage input.
・DC current input of KT2 / KT7 / KT4H / KT4B is supported with an externally connected 50 Ω shunt resistor (sold separately).
Sensor input Thermocouple K, J, R, S, B, E, T, N, PL-II, C (W / Re5-26)
External resistor: Max. 100 Ω (Max. 40 Ω external resistor for B input)
RTD Pt100, JPt100 3-conductor system (Allowable input conductor resistance for each conductor: 10 Ω or less)
DC current 0 to 20 mA DC Input impedance: 50 Ω (For KT2 / KT7 / KT4H / KT4B, connect 50 Ω shunt resistor between input terminals.)
Allowable input current: 50 mA or less (For KT2 / KT7 / KT4H / KT4B, when 50 Ω shunt resistor is used)
4 to 20 mA DC
DC voltage 0 to 1 V DC Input impedance: 1 MΩ or more, Allowable input voltage: 5 V or less, Allowable signal source resistance: 2 kΩ or less
0 to 5 V DC Input impedance: 100 kΩ or more,
Allowable input voltage: 15 V or less, Allowable signal source resistance: 100 Ω or less
1 to 5 V DC
0 to 10 V DC
Control
output
Relay contact (Must be
specified)
1a
3 A 250 V AC (at resistive load), 1 A 250 V AC (at inductive load cos ø = 0.4), Electrical life: 100,000 times
Non-contact
voltage
(voltage output
for SSR drive)
12+20 V DC, Max. load current: 40 mA (with short circuit protection circuit)
DC current 4 to 20 mA DC, Load resistance: Max. 550 Ω
Alarm output 1 (EV1) Relay contact
1a 3 A 250 V AC (Resistive load)
1a 1 A 250 V AC (cosø=0.4)
Electrical life: 100,000 times
Alarm output 2 (EV2) Same as Alarm output 1
Control method PID action (with auto-tuning function), PI action, PD action (with manual reset function), P action (with manual reset function), ON / OFF action
Target temperature setting -
Program control function 1 pattern, 9-step setting is possible (However, make function selection setting of either control with fixed set point or program control.)
Indication
accuracy
Thermocouple Within ± (0.2 % + 1 digit) of each input span or within ±2 ℃ (4 ℉) whichever is greater
However, R or S input; within ±6 ℃ (12 ℉) in the range of 0 to 200 ℃ (32 to 392 ℉)
B input, range of 0 to 300 ℃ (32 to 572 ℉): accuracy is not guaranteed.
K, J, E, T, and N input, less than 0 ℃ (32 ℉): within ± (0.4 % ±1 digit) of input span
RTD Within ± (0.1 % + 1 digit) of each input span or ±1 ℃ (2 ℉) whichever is greater
DC current and DC voltage Within ± (0.2 % + 1 digit) of each input span
Sampling period 125ms
Hysteresis (ON / OFF) Thermocouple and RTD: 0.1 to 1,000.0 ℃ ()
DC current and DC voltage: 1 to 10,000 (The decimal
point place follows the selection)
Proportional band Input without decimal point: 0 to Input span
Input with decimal point: 0.0 to Input span
DC current and DC voltage: 0.0 to 1,000.0 %
Integral time 0 to 3,600 seconds
Derivative time 0 to 1,800 seconds
Proportional cycle 1 to 120 seconds
Allowable voltage fluctuation When 100 to 240 V AC: 85 to 264 V AC, When 24 V AC / DC: 20 to 28 V AC / DC
Insulated resistance 500 V DC, Min. 10 MΩ
Breakdown voltage Between input terminal and power terminal
Between output terminal and power terminal
1.5 kV AC for 1 min.
Malfunction vibration 10 to 55 Hz (1 cycle/min.), single amplitude: 0.35 mm 0.014 in (10 min. on 3 axes)
Breakdown vibration 10 to 55 Hz (1 cycle/min.), single amplitude: 0.75 mm 0.030 in (1 hour on 3 axes)
Malfunction shock X, Y and Z each direction for 5 times 98 m/s2
Breakdown shock X, Y and Z each direction for 5 times 294 m/s2
Ambient temperature −10 to 55 ℃ 14 to 131 ℉
Ambient humidity 35 to 85 % RH (No condensation)
Mass 160 g approx.
Waterproof IP66 (applicable only to the front panel subject to rubber gasket employed)
Display character height PV: 14 mm 0.551 in
SV: 14 mm 0.551 in
Option
functions
Heating /
Cooling
control
Relay contact Using EV2 assigned setting, use for heating and cooling control is possible.
Non-contact
voltage
-
Heater burnout alarm
output
-
Communication function -
Accessories Installation frame /
Mounting bracket
Included with controller
Terminal cover Sold separately
Rubber gasket Included with controller

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)