【Notification of Manufacturer Change for Panasonic Industrial Devices SUNX Products and Panasonic Industrial Devices SUNX Tatsuno Products】
From April 1, 2024, the terms "Panasonic Industrial Devices SUNX Co., Ltd." and "Panasonic Industrial Devices SUNX Tatsuno Co., Ltd."
in this page and in the manuals and other documents to be downloaded will all be replaced with "Panasonic Industry Co., Ltd." and applied accordingly.

AUTOMATION
CONTROLS

Search
Discontinued
Products



PM5S Timers (Discontinued Products)

Rating/ Performance

Type PM5S-A PM5S-S PM5S-M
Item
Rating Rated operating voltage 24 to 240V AC/DC
Rated frequency 50/60Hz common
Rated power consumption 2.6 VA (AC), 1.4 W (DC)
Rated control capacity 5A 250V AC (resistive load)
Operating mode Pulse ON-delay
Pulse Flicker
Pulse ON-Flicker
Signal OFF-delay
Pulse One-shot
Pulse One-cycle
Power ON-delay Pulse ON-delay
Pulse Flicker
Pulse ON-flicker
Signal OFF-delay
Pulse One-shot
Pulse One-cycle
(with instantaneous contact)
Time range 1s to 500h (Max.) 16 time ranges switchable
Time
accuracy
(Note)
Operating time fluctuation ±0.3% (power off time change at the range of 0.1s to 1h)
Setting error ±10% (Full-scale value)
Voltage error ±0.5% (at the operating voltage changes between 85 to 110%)
Temperature error ±2% (at 20℃ ambient temp. at the range of –10 to +55℃ +14 to +131℉)
Contact Contact arrangement Timed-out 2 Form C
Timed-out 1 Form C
Instantaneous 1 Form C
Contact resistance (Initial value) Max. 100mΩ (at 1A 6V DC)
Contact material Silver alloy Au flash on Silver alloy
Life Mechanical (contact) 2 x 107 1 x 107
Electrical (contact) 105 (at rated control capacity)
Electrical
function
Allowable operating voltage range 85 to 110% of rated operating voltage (at 20℃ coil temp.)
Insulation resistance (Initial value) Min. 100MΩ (Between live and dead metal parts, Between input and output, Between contacts of different poles, Between contacts of same pole)
(At 500V DC)
Breakdown voltage (Initial value) 2,000Vrms for 1 min Between live and dead metal parts
2,000Vrms for 1 min Between input and output
2,000Vrms for 1 min Between contacts of different poles
1,000Vrms for 1 min Between contacts of same pole
Min. power off time 100ms
Max. temperature rise 55℃ 131℉ 65℃ 149℉
Mechanical
function
Shock resistance Functional Min. 98m/s2 (4 times on 3 axes)
Destructive Min. 980m/s2 (5 times on 3 axes)
Vibration resistance Functional 10 to 55Hz: 1 cycle/min Single amplitude of 0.35mm (10min on 3 axes)
Destructive 10 to 55Hz: 1 cycle/min Single amplitude of 0.75mm (1h on 3 axes)
Operating
condition
Ambient temperature –10 to +55℃ +14 to +131℉
Ambient humidity Max. 85%RH (non-condensing)
Atmospheric pressure 860 to 1,060hPa
Ripple factor (DC) 20%
Others Protective construction IP40
Weight 120g 4.233 oz
Note 1 :Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage (within 5% ripple factor for DC), 20℃ 68℉ ambient temperature, and 1s power off time.
Note 2 :For the 1s range, the tolerance for each specification becomes ±10ms.

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)