Item | Specifications | |||||||
---|---|---|---|---|---|---|---|---|
Rating | Rated operating voltage | 24VAC | 100 to 120VAC | 200 to 220VAC | 220 to 240VAC | 12VDC | 24VDC | |
Rated frequency | 50/60Hz common | - | ||||||
Rated power consumption | Max. 3 VA (at 24 VAC) |
Max. 3 VA (at 100 VAC) |
Max. 3 VA (at 200 VAC) |
Max. 3 VA (at 220 VAC) |
Max. 2 W (at 12 VDC) |
Max. 2 W (at 24 VDC) |
||
During time delay | Approx. 3mA | Approx. 3mA | Approx. 3mA | Approx. 3mA | Approx. 5mA | Approx. 3mA | ||
After time delay | Approx. 80mA | Approx. 20mA | Approx. 13mA | Approx. 13mA | Approx. 70mA | Approx. 40mA | ||
Rated control capacity | Timed -out 2 Form C: 7A 250V AC (resistive load) | |||||||
Timed -out 4 Form C: 5A 250V AC (resistive load) | ||||||||
Operation mode | S1DXM-A Power on delay operation fixed (Power display: ON/green; Operation display (when output is on): UP/orange) |
|||||||
S1DXM-M 4 switchable operations: Power ON-delay/Power Flicker OFF start/Power Flicker ON start/Power One-shot (Power display: ON/green; Operation display (when output is on): UP/orange) |
||||||||
Time accuracy*1 | Operating time fluctuation & Power off time change error | Max. ±1 %, (power off time change at the range of 0.1 s to 1 h), 1 s range: Max. ±1 % and 10 ms*2 | ||||||
Voltage error | Max. ±1 % (at the operating voltage changes between -20 to +10%), 1 s range: Max. ±1 % and 10 ms*2 | |||||||
Temperature error | Max. ±5% (at 20°C ambient temp. at the range of -10 to +50°C/ +14 to +122°F) | |||||||
Setting error | Max. ±10%, 1 s range: Max. ±10% and 20 ms | |||||||
Contact | Contact arrangement | Timed-out 2 Form C, Timed-out 4 Form C | ||||||
Contact resistance (Initial value) | Max. 100mohm (at 1A, 6V DC) | |||||||
Contact material | Timed-out 2 Form C type: Silver alloy, Au plating | |||||||
Timed-out 4 Form C type: Silver alloy, Au plating | ||||||||
Life | Mechanical (constant) | Min. 107 | ||||||
Electrical (constant) | 2 × 105(at rated control capacity) | |||||||
Mechanical | Vibration resistance | Functional | 10 to 55Hz: 1 cycle/min double amplitude of 0.25mm (10min on 3 axes) | |||||
Destructive | 10 to 55Hz: 1 cycle/min double amplitude of 0.375mm (1h on 3 axes) | |||||||
Shock resistance | Functional | Min. 98m/s2 (4 times on 3 axes) | ||||||
Destructive | Min. 980m/s2 (5 times on 3 axes) | |||||||
Electrical | Allowable operating voltage range | 80 to 110% of rated operating voltage | ||||||
Reset time | Max. 0.1s | |||||||
Insulation resistance (Initial value) | Between live and dead metal parts, between input and output, between contact sets, between contacts Min. 100 Mohm (at 500 V DC megger) | |||||||
Breakdown voltage (Initial value) |
Between live and dead metal parts: 2,000 Vrms for 1 min Between input and output: 2,000 Vrms for 1 min Between contact sets: 2,000 Vrms for 1 min Between contacts: 1,000 Vrms for 1 min |
|||||||
Max. temperature rise | 70°C/ 158°F | |||||||
Operating conditions | Ambient temperature | -10 to 50°C/ +14 to 122°F | ||||||
Ambient humidity | 35 to 85% RH (non-condensing) | |||||||
Air pressure | 860 to 1060 hPa | |||||||
Ripple rate | DC type only, transmission wave rectification (ripple rate: approx. 48%)*3 | |||||||
Mass (Weight) | Approx. 45 g | |||||||
Protective construction | IEC standard: IP40 (IP50 when using ADX18008 protective cover) |
*1 Unspecified measuring conditions are rated operating voltage (in case of DC type, ripple rate of 5% or less), ambient temp. 20℃/ 68℉, and power off time 1 second.
*2 Power one-shot 1 s range: +2% and 10 ms
*3 When using with a transmission wave rectification, vibration resistance and shock resistance properties worsen compared to when using a stabilized power supply.
Following products will be discontinued in the end of September, 2020.
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)