AFPXHC14□ / AFPXHC30□ / AFPXHC60□
Item | Specifications | |||
---|---|---|---|---|
Operating ambient temperature | 0 to +55 ℃ +32 to +131 ℉ | |||
Storage ambient temperature | -40 to +70 ℃ -40 to +158 ℉ | |||
Operating ambient humidity | 10 to 95 % RH (at +25 ℃ +77 ℉, non-condensing) | |||
Storage ambient humidity | 10 to 95 % RH (at +25 ℃ +77 ℉, non-condensing) | |||
Breakdown voltage (Note) |
AC power supply | DC power supply | ||
Relay output | Between power supply terminal and earth terminal | 1,500 V AC for 1 minute | 500 V AC for 1 minute | |
Between power supply terminal and service power supply terminal | 1,500 V AC for 1 minute | - | ||
Between input terminal and earth terminal | 1,500 V AC for 1 minute | 500 V AC for 1 minute | ||
Between output terminal and earth terminal | 1,500 V AC for 1 minute | 1,500 V AC for 1 minute | ||
Transistor output |
Between power supply terminal and earth terminal | 1,500 V AC for 1 minute | 500 V AC for 1 minute | |
Between power supply terminal and service power supply terminal | 1,500 V AC for 1 minute | - | ||
Between input terminal and earth terminal | 1,500 V AC for 1 minute | 500 V AC for 1 minute | ||
Between output terminal and earth terminal | 500 V AC for 1 minute | 500 V AC for 1 minute | ||
Isolation resistance |
Between power supply terminal and earth terminal | 100 MΩ or more (500 V DC using an insulation resistance meter) |
||
Between power supply terminal and service power supply terminal | ||||
Between input terminal and earth terminal | ||||
Between output terminal and earth terminal | ||||
Vibration resistance |
5 to 8.4 Hz, 3.5 mm 0.138 in single amplitude 8.4 to 150 Hz, Acceleration 9.8 m/s2 10 min. each in the X, Y and Z directions (1 octave/min) |
|||
Shock resistance | 147 m/s2, 4 times each in the X, Y and Z directions | |||
Noise resistance | 1,000 V [P-P] with pulse widths of 50 ns and 1 μs (using a noise simulator) (Power supply terminal) |
|||
Operating condition | No corrosive gas and no excessive dust | |||
Applicable standard for EC directives |
EMC directive: EN 61131-2 (directive concerning emission, immunity and low voltage) |
|||
Over-voltage category | Category II | |||
Level of contamination | 2 |
Note: | Cut-off current 5 mA (Initial value at shipment) |
---|
AFPXHC14□ / AFPXHC30□ / AFPXHC60□
Item | Specifications | ||
---|---|---|---|
Programming method | Relay symbol | ||
Control method | Cyclic operation | ||
Program memory | Built-in Flash ROM | ||
Program capacity | C14: 16 k steps, C30 / C60: 24 k / 32 k / 40 k steps (switch-over) (Note 1) |
||
Basic instructions | Approx. 110 | ||
High-level instructions | Approx. 220 | ||
Operation speed | [Basic instruction (ST)] Approx. 0.04 μs/step (under 7 k steps) Approx. 0.7 μs/step (7 k steps or more) [High-level instruction (F0MV)] Approx. 0.22 μs/step (under 7 k steps) Approx. 1.73 μs/step (7 k steps or more) |
||
Operation memory |
Link relay |
External input (X) (Note 2) | 1,760 points (X0 to X109F) |
External output (Y) (Note 2) | 1,760 points (Y0 to Y109F) | ||
Internal relay (R) (Note 3) | Default: 8,192 points (R0 to R511F) FP-X compatible specifications: 4,096 points |
||
Special internal relay (R) | 240 points | ||
Timer / Counter (T / C) (Note 4) | 1,024 points (Initial settings Timer: 1,008 points, Counter: 16 points) | ||
Link relay (L) | 2,048 points (L0 to L127F) | ||
Memory area |
Data register (DT) | C14: 12 k words, C30 / C60: 64 k, 32 k, 12 k words * For C30 / C60, DT capacity varies according to the program capacity |
|
Special data register (DT) | 500 words | ||
Link data register (LD) | 256 words (LD0 to LD255) | ||
File register (FL) | None | ||
Index register (I) | 14 words (I0 to ID) | ||
Differential points | Points for program capacity | ||
Master control relay points (MCR) | 256 points | ||
Number of labels (JMP + LOOP) | 256 points | ||
Number of step ladders | 1,000 steps | ||
Number of subroutines | 500 subroutines | ||
Number of interrupt program | Transistor output type: Input 8, Constant 1 Relay output type: Input 11 (for C30 / C60: 14), Constant 1 |
||
High-speed counter (Note 5) (Note 6) |
Control unit input | [Transistor output type] Single-phase 8 channels (100 kHz × 4, 10 kHz × 4) or 2-phase 4 channels (50 kHz × 2, 10 kHz × 2) [Relay output type] Single-phase 8 channels (10 kHz × 8) or 2-phase 4 channels (10 kHz × 4) |
|
Pulse I/O with cassette installed |
[Transistor output type] Installation not possible [Relay output type] C14: Single-phase 2 channels (100 kHz × 2) or 2-phase 1 channel (50 kHz × 1) C30 / C60: Single-phase 4 channels (100 kHz × 4) or 2-phase 2 channels (50 kHz × 2) *with two cassettes installed |
||
Pulse output / PWM output (Note 5) (Note 6) |
Control unit output | [Transistor output type] C14: 3 channels, C30: 4 channels, C60: 6 channels [Pulse output] each 100 kHz [PWM output] 3 channels (C14), 4 channels (other than C14) 1 Hz to 70 kHz (Resolution of 1000) 70.001 kHz to 100 kHz (Resolution of 100) |
|
Pulse I/O with cassette installed |
[Relay output type] C14: 1 channel, C30 / C60: 2 channels *with two cassettes installed [Pulse output] each 100 kHz [PWM output] 1 channel (C14), 2 channels (other than C14) *with two cassettes installed 1 Hz to 70 kHz (Resolution of 1000) 70.001 kHz to 100 kHz (Resolution of 100) |
||
Pulse catch input Interrupt input (Note 6) |
[Transistor output type] 8 points (Control unit input: 8 points) [Relay output type] 14 points (Control unit input: 8 points, Pulse I/O cassette : 3 points × 2) |
||
Periodical interrupt (Note 6) | 0.1 ms to 30 sec. | ||
Potentiometer input | 1 channel (0 to 4,000) | ||
Input time constant processing | Available | ||
Clock / calendar | Available (only when the master memory cassette AFPX-MRTC and battery are installed) | ||
Flash ROM backup |
Backup by F12 / P13 instructions | All area of Data register | |
Automatic backup when power is off |
Counter: 16 points, Internal relay: 128 points, Data register: 315 words |
||
Battery backup | Memory set in hold area of system register (only when battery is installed) |
||
Battery lifetime | 5 years or more in the actual use condition (operating 8 hours a day) (Note 7) |
||
Password | Yes (Can be selected from 4 digits, 8 digits or 32 digits) | ||
Self-diagnostic function | Watchdog timer, program syntax check, etc. | ||
PLC link function | Max. 16 units, link relay: 1,024 points, link register: 128 words (Data transfer, remote programming: Not available) |
||
Rewriting in RUN mode | Available (downloading in RUN mode, program rewriting in RUN mode) (Max. 512 steps) |
Notes:
1) | When changing the system register No.0 (sequence program capacity), the data register (DT) capacity will also change. |
---|---|
2) | The number of points in the table is the number of points of operation memory. The number of points actually available to be used is determined by the hardware configuration. |
3) | Can be selected by the setting of the system register No. 1 (internal relay capacity). To provide compatibility with the conventional FP-X series control unit, select 4,096 points. |
4) | The number of timer points can be changed by the setting of the system register No.5. |
5) | The maximum counting speed and maximum output frequency for the high-speed counter, pulse output and PWM output indicate the specifications for the voltage of 24 V DC and ambient temperature of +25 ℃ +77 ℉. The frequency may decrease depending on voltage, temperature or combination of functions used. |
6) | The inputs and outputs used for each function of the high-speed counter, pulse output, PWM output, pulse catch input or interrupt input cannot be allocated in duplication. |
7) | Battery lifetime values is calculated when the power is not completely turned on. Since the actual value depends on conditions of use, in practice, the lifetime may be shorter. |
|
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]