AUTOMATION
CONTROLS

Search
Discontinued
Products



Head-separated Dual display Digital Pressure Sensor [For gas & liquid] DPC-L100 / DPH-L100

Specifications

Sensor heads

Type Compound pressure Positive pressure
-0.1 to 1 MPa type 1 MPa type 3.5 MPa type 10 MPa type 50 MPa type
Model No. DPH-L113V DPH-L113 DPH-L133 DPH-L114 DPH-L154
Applicable regulations CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations)
Type of pressure Sealed gauge pressure (Note 4)
Rated pressure range -0.1 to +1 MPa 0 to +1 MPa 0 to +3.5 MPa 0 to +10 MPa 0 to +50 MPa
Pressure withstandability 2 MPa 2 MPa 7 MPa 20 MPa 75 MPa
Applicable fluid Gases and fluids that do not corrode stainless steel SUS630, SUS304, or SUSXM7
Supply voltage 9 to 36 V DC
[9 to 32 V DC when using the attached connector (e-CON)]
Current consumption 20 mA or less
Analog voltage output Output voltage: 1 to 5 V DC (over rated pressure range)
Accuracy: ±1.0 % F.S. (at 23 ±2 ℃ +73.4 ±35 ℉)
±2.0 % F.S. (at -20 to 70 ℃ -4 to +158 ℉)
(including linearity, hysteresis and repeatability)
Output voltage: 1 to 5 V DC (over rated pressure range)
Accuracy: ±1.0 % F.S. (at 23 ±2 ℃ +73.4 ±35 ℉)
±2.0 % F.S. (at -20 to 125 ℃ -4 to +257 ℉)
(including linearity, hysteresis and repeatability)
Response time 1 ms or less
Protection IP67 (IEC)
Ambient temperature -20 to +70 ℃ -4 to +158 ℉ (No dew condensation or icing allowed),
Storage: -30 to +70℃ -22 to +158 ℉
-20 to +80 ℃ (Pressure port: -20 to +125 ℃
-4 to +257 ℉, No dew condensation or icing allowed),
Storage: -30 to +100 ℃ -22 to +212 ℉
[e-CON connector (accesory):
-20 to +75 ℃
-4 to +167 ℉
(Storage: -30 to +75 ℃ -22 to +167 ℉)]
Ambient humidity 35 to 85 % RH, Storage: 35 to 85 % RH
Medium temperature range -20 to +70 ℃ -4 to +158 ℉ -20 to +125 ℃ -4 to +257 ℉
Voltage withstandability 150 V AC for one min. between all supply terminals connected together and enclosure
Insulation resistance 100 MΩ, or more, with 50 V DC megger between all supply terminals connected together and enclosure
Vibration resistance 10 to 2,000 Hz frequency, acceleration 200 m/s2, in X direction for four hours, in Y and Z directions for two hours each (Note 5)
Shock resistance 1,000 m/s2 acceleration in X, Y and Z directions three times each
Grounding method Capacitor earth (Enclosure-supply terminal)
Pressure port R1/4 male thread (throttle embeded)
Material Diaphragm: Stainless steel (SUS603), Pressure port: Stainless steel (SUS304), Throttle: Stainless steel (SUSXM7)
Connecting method Connector
Cable 0.2 mm2 3-core heat resistant cabtyre cable 2 m 3.562 ft long
Cable extension Extension up to total 10 m 32.808 ft is possible with 0.2 mm2, or more, cable.
Weight Net weight: 100 g approx., Gross weight: 150 g approx.
Accessory Connector (e-CON): 1 pc.

Notes:

1) Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23 ℃ +73.4 ℉.
2) The sensor head can be used independently.
3) Oil is used in the factory inspection process for models DPH-L114 and DPH-L154. There may be some residual oil inside the pressure port.
4) The sensor’s internal mechanism is sealed based on an air pressure of 1,013 hPa.
5) The X, Y, and Z directions are defined as follows:

Controllers

NPN output DPC-L101
PNP output DPC-L101-P
Applicable regulations CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations)
Applicable sensor head DPH-L113V DPH-L113 DPH-L133
Rated pressure range -0.1 to +1 MPa 0 to +1 MPa 0 to +3.5 MPa
Set pressure range -1.177 to +1.177 MPa
-12.00 to +12.00 kgf/cm2
-11.77 to +11.77 bar
-170.6 to +170.6 psi
-1.070 to +1.070 MPa
-10.91 to +10.91 kgf/cm2
-10.70 to +10.70 bar
-155.2 to +155.2 psi
-3.74 to +3.74 MPa
-38.1 to +38.1 kgf/cm2
-37.4 to +37.4 bar
-542 to +542 psi
Set resolution 0.001 MPa 0.001 MPa 0.01 MPa
Display 4 digits +4 digits 3-color LCD display
(Display refresh rate: 250 ms, 500 ms, 1,000 ms, selectable by key operation)
  Displayable pressure range -0.155 to +1.022 MPa
-1.58 to +10.42 kgf/cm2
-1.55 to +10.22 bar
-22.4 to +148.2 psi
-0.050 to +1.020 MPa
-0.51 to +10.40 kgf/cm2
-0.50 to +10.20 bar
-7.2 to +148.0 psi
-0.17 to +3.57 MPa
-1.7 to +36.4 kgf/cm2
-1.7 to +35.7 bar
-24 to +518 psi
Supply voltage 12 to 24 V DC ±10 % Ripple P-P 10 % or less
Power consumption Normal operation: 960 mW or less (Current consumption 40 mA or less at 24 V supply voltage)
ECO mode (STD): 720 mW or less (Current consumption 30 mA or less at 24 V supply voltage)
ECO mode (FULL): 600 mW or less (Current consumption 25 mA or less at 24 V supply voltage)
Excluding the current consumption of sensor head and analog output current
Comparative outputs
(Comparative output 1, 2)
<NPN output type>
NPN open-collector transistor (2 outputs)
• Maximum sink current: 50 mA
• Applied voltage: 30 V DC or less
(between comparative output and 0 V)
• Residual voltage: 1 V or less (at 50 mA sink current)

<PNP output type>
PNP open-collector transistor (2 outputs)
• Maximum source current: 50 mA
• Applied voltage: 30 V DC or less
(between comparative output and +V)
• Residual voltage: 1 V or less (at 50 mA source current)
  Output operation NO / NC, selectable by key operation
Output modes EASY mode / Hysteresis mode / Window comparator mode
Hysteresis Minimum 1 digit (variable) (however, 2 digits when using psi unit)
Repeatability Within ±0.2 % F.S.
Response time 5 ms, 10 ms, 25 ms, 50 ms, 100 ms, 250 ms, 500 ms, 1,000 ms, 5,000 ms, selectable by key operation
Short-circuit protection Incorporated
Analog output <Analog voltage output>
• Output current: 1 to 5 V DC
• Zero point: within 1 V ±0.5 % F.S. (excluding DPH-L113V) within 1.364 V ±0.5 % F.S. (DPH-L113V)
• Span: within 4 V ±0.5 % F.S.
• Linearity: within ±0.1 % F.S.
• Output impedance: 1 kΩ approx.

<Analog current output>
• Output current: 4 to 20 mA
• Zero point: within 4 mA ±1.0 % F.S. (excluding DPH-L113V) within 5.455 mA ±1.0 % F.S. (DPH-L113V)
• Span: within 16 mA ±1.5 % F.S.
• Linearity: within ±0.1 % F.S.
• Load resistance: 250 Ω (max.)
Inputs Sensor head input Input voltage range: 1 to 5 V DC (over rated pressure range)
External input <NPN output type>
ON voltage: 0.4 V DC or less
OFF voltage: 5 to 30 V DC, or open
Input impedance: 10 kΩ approx.
Input time: 1 ms or more

<PNP output type>
ON voltage: 5 V to +V DC
OFF voltage: 0.6 V DC or less, or open
Input impedance: 10 kΩ approx.
Input time: 1 ms or more
Operation indicator Orange LED
(Comparative output 1 operation indicator, comparative output 2 operation indicator: Lights up when each comparative output is ON )
Protection IP40 (IEC)
Ambient temperature -10 to +50 ℃ +14 to +122 ℉ (No dew condensation or icing allowed), Storage: -10 to +60 ℃ +14 to +140 ℉
Ambient humidity 35 to 85 % RH, Storage: 35 to 85 % RH
Voltage withstandability 500 V AC for one min. between all supply terminals connected together and enclosure
Insulation resistance 50 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure
Vibration resistance 10 to 500 Hz frequency, double amplitude 3 mm 0.118 in or maximum acceleration 196 m/s2, in X, Y and Z directions for two hours each (when panel mounting bracket is mounted: 10 to 150 Hz frequency, double amplitude 0.75 mm 0.030 in or maximum acceleration 49 m/s2, in X, Y and Z directions for two hours each)
Shock resistance 100 m/s2 acceleration in X, Y and Z directions three times each
Temperature characteristics Within ±0.5 % F.S. (ambient temperature range based on +20 ℃ +68 ℉)
Material Enclosure: PBT (glass fiber reinforced),
LCD display: Acrylic,
Mounting threaded part: Brass (nickel plated),
Switch part: Silicone rubber
Connecting method Connector
Cable length Total length up to 100 m 328.084 ft (less than 30 m 98.425 ft when conforming to CE marking) is possible with 0.3 mm2, or more, cable.
Weight Net weight: 25 g approx. (excluding connector attached cable),
Gross weight: 140 g approx.
Accessories CN-66A-C2 (Connector attached cable 2 m 6.562 ft), Pressure unit label: 1 set

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)