【Notification of Manufacturer Change for Panasonic Industrial Devices SUNX Products and Panasonic Industrial Devices SUNX Tatsuno Products】
From April 1, 2024, the terms "Panasonic Industrial Devices SUNX Co., Ltd." and "Panasonic Industrial Devices SUNX Tatsuno Co., Ltd."
in this page and in the manuals and other documents to be downloaded will all be replaced with "Panasonic Industry Co., Ltd." and applied accordingly.
Business > Industrial Devices > Automation Controls Top > FA Sensors & Components > Pressure Sensors / Flow Sensors > Pressure Sensors / Flow Sensors > Head-separated Dual Display Digital Pressure Sensor [For Gas] DPH-100 / DPC-100 > Specifications
Type | Compound pressure | Positive pressure | Vacuum pressure | ||||||
---|---|---|---|---|---|---|---|---|---|
±100 kPa type | 1 MPa type | -101 kPa type | |||||||
Model No.(Note 3) | DPH-101(-R) | DPH-101-M3(-R) | DPH-101-M5(-R) | DPH-102 | DPH-102-M5(-R) | DPH-103(-R) | DPH-103-M3(-R) | DPH-103-M5(-R) | |
CE marking directive compliance | EMC Directive, RoHS Directive | ||||||||
Type of pressure | Gauge pressure | ||||||||
Rated pressure range | -100.0 to +100.0 kPa | 0 to +1.000 MPa | 0 to -101.0 kPa | ||||||
Pressure withstandability | 500 kPa | 1.5 MPa | 500 kPa | ||||||
Applicable fluid | Air, non-corrosive gas | ||||||||
Supply voltage | 12 to 24 V DC ± 10 % Ripple P-P 10 % or less | ||||||||
Current consumption | 15 mA or less | ||||||||
Analog voltage output | Output voltage: 1 to 5 V (over rated pressure range) Zero point: within 1 V ± 2.5 % F.S. (vacuum / positive pressure type) within 3 V ± 3 % F.S. (compound pressure type) Span: within 4 V ± 3.5 % F.S. Linearity: within ±0.5 % F.S. Output impedance: 1 kΩ approx. |
||||||||
Protection | IP40 (IEC) | ||||||||
Ambient temperature | 0 to +50 ℃ +32 to +122 ℉ (No dew condensation allowed), Storage: -10 to +60 ℃ +14 to +140 ℉ | ||||||||
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH | ||||||||
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure | ||||||||
Insulation resistance | 50 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure | ||||||||
Vibration resistance | 10 to 500 Hz frequency, double amplitude 3 mm 0.118 in or maximum acceleration 196 m/s2, in X, Y and Z directions for two hours each | ||||||||
Shock resistance | 1,000 m/s2 acceleration (100 G approx.) in X, Y and Z directions three times each | ||||||||
Temperature characteristics | Over ambient temperature range 0 to +50 ℃ +32 to +122 ℉: within ±2 % F.S. of detected pressure at +25 ℃ +77 ℉ | ||||||||
Pressure port | DPH-10□(-R): R1/8 male thread + M5 female thread, DPH-10□-M3(-R): M3 male thread (for installing gasket) DPH-10□-M5(-R): M5 male thread (for installing gasket) |
||||||||
Material | Front case: PBT, Rear case: PBT (glass fiber reinforced), Pressure port: Stainless steel (SUS303), O-ring: NBR Pressure element: Silicon diaphragm, PPS |
||||||||
Connecting method | Connector | ||||||||
Cable | 0.2 mm2 4-core oil resistant cabtyre cable (Models with "-R" affixed to the Model No. have flexible, oil-resistant cabtyre cable) | ||||||||
Cable extension | Extension up to total 10 m 32.808 ft is possible with 0.2 mm2, or more, cable. | ||||||||
Weight | Net weight | DPH-10□(-R): Head 10 g approx. / Cable 40 g approx., DPH-10□-M3/M5(-R): Head 6 g approx. / Cable 40 g approx. | |||||||
Gross weight | DPH-10□(-R): 80 g approx., DPH-10□-M3/M5(-R): 70 g approx. | ||||||||
Accessory | Connector (e-CON): 1 pc. |
Note 1 : | Where measurement conditions have not been specifi ed precisely, the conditions used were an ambient temperature of +25 ℃ +77 ℉. |
---|---|
Note 2 : | The sensor head can be used independently. |
Note 3 : | Model No. having the suffix "-R" is bending-resistant cable type. The bending-resistant cable type of DPH-102 is not available. |
Type | NPN output type | PNP output type | |
---|---|---|---|
Model No. | DPC-101 | DPC-101-P | |
CE marking directive compliance | EMC Directive, RoHS Directive | ||
Applicable sensor head | DPH-101□, DPH-102□, DPH-103□ | ||
Rated pressure range (Note 2) |
Compound pressure: -100.0 to +100.0 kPa, Positive pressure: 0 to +1.000 MPa, Vacuum pressure: 0 to -101.0 kPa |
||
Set pressure range (Note 2) |
Compound pressure: -199.9 to +199.9 kPa (-1.999 to +1.999 kgf/cm2, -19.98 to +19.98 psi, -1.999 to +1.999 bar, -1510 to +1537 mmHg, -59.4 to +60.5 inHg) Positive pressure: -1.050 to +1.050 MPa (-10.71 to +10.71 kgf/cm2, -152.2 to +152.2 psi, -10.50 to +10.50 bar) Vacuum pressure: +101.3 to -101.3 kPa (+1.033 to -1.033 kgf/cm2, +14.70 to -14.70 psi, +1.013 to -1.013 bar, +760 to -760 mmHg, +29.9 to -29.9 inHg) |
||
Supply voltage | 12 to 24 V DC ± 10 % Ripple P-P 10 % or less | ||
Power consumption | Normal operation: 960 mW or less (Current consumption 40 mA or less at 24 V supply voltage) ECO mode (STD): 720 mW or less (Current consumption 30 mA or less at 24 V supply voltage) ECO mode (FULL): 600 mW or less (Current consumption 25 mA or less at 24 V supply voltage) Excluding the current consumption of sensor head and analog output current |
||
Sensor head supply voltage | Same as supply voltage | ||
Comparative outputs (Comparative output 1, 2) |
NPN open-collector transistor (2 outputs) ・Maximum sink current: 100 mA ・Applied voltage: 30 V DC or less (between comparative output and 0 V) ・Residual voltage: 2 V or less (at 100 mA sink current) |
PNP open-collector transistor (2 outputs) ・Maximum source current: 100 mA ・Applied voltage: 30 V DC or less (between comparative output and +V) ・Residual voltage: 2 V or less (at 100 mA source current) |
|
Output operation | NO / NC, selectable by key operation | ||
Output modes | EASY mode / Hysteresis mode / Window comparator mode | ||
Hysteresis | Minimum 1 digit (variable) (however, 2 digits when using psi unit) | ||
Repeatability | With vacuum / positive pressure type connected: within ±0.2 % F.S. (±2 digits) With compound pressure type connected: within ±0.2 % F.S. (±4 digits) |
||
Response time | 0.5 ms, 1 ms, 2.5 ms, 5 ms, 10 ms, 25 ms, 50 ms, 100 ms, 250 ms, 500 ms, 1,000 ms, 5,000 ms, selectable by key operation | ||
Short-circuit protection | Incorporated | ||
Analog output | <Analog voltage output> ・Output current: 1 to 5 V DC ・Zero point: within 1 V ± 0.5 % F.S. (vacuum / positive pressure type) within 3 V ± 0.5 % F.S. (compound pressure type) ・Span: within 4 V ± 0.5 % F.S. ・Linearity: within ±0.1 % F.S. ・Output impedance: 1 kΩ approx. <Analog current output> ・Output current: 4 to 20 mA ・Zero point: within 4 mA ± 1 % F.S. (vacuum / positive pressure type) within 12 mA ± 1.5 % F.S. (compound pressure type) ・Span: within 16 mA ± 1.5 % F.S. ・Linearity: within ±0.1 % F.S. ・Load resistance: 250 Ω (max.). |
||
Inputs | Sensor head input | Input voltage range: 1 to 5 V DC (over rated pressure range) | |
External input (Auto-reference function/Remote zero-adjustment function) |
ON voltage: +0.4 V DC or less OFF voltage: +5 to +30 V DC, or open Input impedance: 10 kΩ approx. Input time: 1 ms or more |
ON voltage: +5 V to +V DC OFF voltage: +0.6 V DC or less, or open Input impedance: 10 kΩ approx. Input time: 1 ms or more |
|
Display | 4 digits + 4 digits 3-color LCD display (Display refresh rate: 250 ms, 500 ms, 1,000 ms, selectable by key operation) | ||
Displayable pressure range | Vacuum pressure: +5.1 to -101.3 kPa, Positive pressure: -0.050 to +1.020 MPa, Compound pressure: -101.3 to +105.0 kPa |
||
Operation indicator | Orange LED (Comparative output 1 operation indicator, comparative output 2 operation indicator: Lights up when each comparative output is ON) | ||
Protection | IP40 (IEC) | ||
Ambient temperature | -10 to +50 ℃ +14 to +122 ℉ (No dew condensation or icing allowed), Storage: -10 to +60 ℃ +14 to +140 ℉ | ||
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH | ||
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure | ||
Insulation resistance | 50 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure | ||
Vibration resistance | 10 to 500 Hz frequency, double amplitude 3 mm 0.118 in or maximum acceleration 196 m/s2, in X, Y and Z directions for two hours each (when panel mounting bracket is mounted : 10 to 150 Hz frequency, double amplitude 0.75 mm 0.030 in or maximum acceleration 49 m/s2, in X, Y and Z directions for two hours each) | ||
Shock resistance | 100 m/s2 acceleration (10 G approx.) in X, Y and Z directions three times each | ||
Temperature characteristics | Within ±0.5 % F.S. (ambient temperature range based on +20 ℃ +68 ℉) | ||
Material | Enclosure: PBT (glass fiber reinforced), LCD display: Acrylic, Mounting threaded part: Brass (nickel plated), Switch part: Silicone rubber | ||
Connecting method | Connector | ||
Cable length | Total length up to 100 m 328.084 ft is possible with 0.3 mm2, or more, cable. | ||
Weight | Net weight: 25 g approx. (excluding connector attached cable), Gross weight: 140 g approx. | ||
Accessories | CN-66A-C2 (Connector attached cable 2 m 6.562 ft), Pressure unit label: 1 set |
Note 1 : | Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20 ℃ +68 ℉. |
---|---|
Note 2 : | It changes automatically according to the connected pressure sensor head. |
Note 3 : | The values specified above are applied only to the controller. |
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])