Safety Light Curtain Type 4 Korean Press Machine Compliant SF4B-03 Ver.2 (Discontinued Products)

I/O Circuit and Wiring diagrams

I/O circuit diagram

<In case of using I/O circuit for PNP output>

I/O circuit diagram In case of using I/O circuit for PNP output
Note: The above diagram is when using a 12-core cable. If an 8-core cable is used, the red, yellow, gray, gray / black, sky-blue / white and sky-blue / black lead wires are absent.

*S1

Switch S1
Emission halt input / Reset input
For manual reset
Vs to Vs – 2.5 V (sink current 5 mA or less): Emission halt (Note 1)
Open: Emission
For automatic reset
Vs to Vs – 2.5 V (sink current 5 mA or less): Emission (Note 1)
Open: Emission halt
Interlock setting input, Override input, Muting input A / B,
External device monitoring input
Vs to Vs – 2.5 V (sink current 5 mA or less): Enabled (Note 1)
Open: Disabled
Note: Vs is the applying supply voltage.


<In case of using I/O circuit for NPN output>

I/O circuit diagram In case of using I/O circuit for NPN output
Note: The above diagram is when using a 12-core cable. If an 8-core cable is used, the red, yellow, gray, gray / black, sky-blue / white and sky-blue / black lead wires are absent.

*S1

Switch S1
Emission halt input / Reset input
For manual reset
0 to +1.5 V (source current 5 mA or less): Emission halt
Open: Emission
For automatic reset
0 to +1.5 V (source current 5 mA or less): Emission
Open: Emission halt
Interlock setting input, Override input, Muting input A / B,
External device monitor input
0 to +1.5 V (source current 5 mA or less): Enabled
Open: Disabled


Connection example

Standard components (8-core cable): Interlock function “enabled (manual reset)”, external device monitoring function “enabled”

<In case of using I/O circuit for PNP output>

Connection example In case of using I/O circuit for PNP output

*S1

Switch S1
Emission halt input / Reset input
For manual reset
Vs to Vs – 2.5 V (sink current 5 mA or less): Emission halt (Note)
Open: Emission
For automatic reset
Vs to Vs – 2.5 V (sink current 5 mA or less): Emission (Note)
Open: Emission halt
Note: Vs is the applying supply voltage.

The diagram at above shows the configuration when using PNP output, interlock function “enabled (manual reset)” and external device monitoring function “enabled”.

In case of setting the interlock function to “disabled (automatic reset)”
Connection example In case of setting the interlock function to “disabled (automatic reset)”

*Refer to the SF4B<V2> instruction manual for details of the interlock function.


In case of setting the external device monitoring function to “disabled”
Connection example In case of setting the external device monitoring function to “disabled”

*Refer to the SF4B<V2> instruction manual for details of the external device monitoring function.



<In case of using I/O circuit for NPN output>

Connection example In case of using I/O circuit for NPN output

*S1

Switch S1
Emission halt input / Reset input
For manual reset
0 to +1.5 V (source current 5 mA or less): Emission halt
Open: Emission
For automatic reset
0 to +1.5 V (source current 5 mA or less): Emission
Open: Emission halt

The diagram at above shows the configuration when using NPN output, interlock function “enabled (manual reset)” and external device monitoring function “enabled”.


In case of setting the interlock function to “disabled (automatic reset)”
Connection example In case of setting the interlock function to “disabled (automatic reset)”

*Refer to the SF4B<V2> instruction manual for details of the interlock function.


In case of setting the external device monitoring function to “disabled”
Connection example In case of setting the external device monitoring function to “disabled”

*Refer to the SF4B<V2>instruction manual for details of the external device monitoring function.



Connection example

Muting control components (12-core cable, with interference prevention wires): Interlock function “disabled (automatic reset)”, external device monitoring function “disabled”

<In case of using I/O circuit for PNP output>

Connection example In case of using I/O circuit for PNP output

*S1

Switch S1
Emission halt input / Reset input
For manual reset
Vs to Vs – 2.5 V (sink current 5 mA or less): Emission halt (Note), Open: Emission
For automatic reset
Vs to Vs – 2.5 V (sink current 5 mA or less): Emission (Note), Open: Emission halt
Override input, Muting input A / B, External device monitoring input
Vs to Vs – 2.5 V (sink current 5 mA or less): Enabled (Note), Open: Disabled
Note: Vs is the applying supply voltage.

The diagram at above shows the configuration when using PNP output, interlock function “disabled (automatic reset)” and external device monitoring function “disabled”.


In case of setting the interlock function to “enabled (manual reset)”
  • When the interlock function is “enabled (manual reset)”, the override function cannot be used.
Connection example In case of setting the interlock function to “enabled (manual reset)”

*Refer to the SF4B<V2> instruction manual for details of the interlock function.


In case of setting the external device monitoring function to “enabled”
Connection example In case of setting the external device monitoring function to “enabled”

*Refer to the SF4B<V2> instruction manual for details of the external device monitoring function.


<In case of using I/O circuit for NPN output>

Connection example In case of using I/O circuit for NPN output

*S1

Switch S1
Emission halt input / Reset input
For manual reset
0 to +1.5 V (source current 5 mA or less): Emission halt, Open: Emission
For automatic reset
0 to +1.5 V (source current 5 mA or less): Emission, Open: Emission halt
Override input, Muting input A / B, External device monitoring input
0 to +1.5 V (source current 5 mA or less): Enabled, Open: Disabled

The diagram at above shows the configuration when using NPN output, interlock function “disabled (automatic reset)” and external device monitoring function “disabled”.


In case of setting the interlock function to “enabled (manual reset)”
  • When the interlock function is “enabled (manual reset)”, the override function cannot be used.
Connection example In case of setting the interlock function to “enabled (manual reset)”

*Refer to the SF4B<V2> instruction manual for details of the interlock function.


In case of setting the external device monitoring function to “enabled”
Connection example In case of setting the external device monitoring function to “enabled”

*Refer to the SF4B<V2> instruction manual for details of the external device monitoring function.



SF-C11

SF4B / SF4B-G series wiring diagram (Control Category 4)

For PNP output (minus ground)
  • Set the safety light curtain input polarity selection switch to the PNP side and ground the 0 V line.
SF-C11 For PNP output (minus ground)

Notes:

1) The above diagram is when using manual reset. If automatic reset is used, disconnect the lead from X2 and connect it to X3. In this case, a reset (RESET) button is not needed.
2) Use a momentary-type switch as the reset (RESET) button.
3) Emission halt occurs when the test (TEST) button is open, and emission occurs when the test (TEST) button is short-circuited. If not using the test (TEST) button, short-circuit T1 and T2.

For NPN output (plus ground)
  • In the above diagram, set the safety light curtain input polarity selection switch to the NPN side and ground the + side.
     SF4B series wiring diagram (Control Category 4) For NPN output (plus ground)

When SF-C11 is connected to the safety light curtain, be sure to use the following mating cable.
SFB-CB□, SFB-CCJ10□


Terminal arrangement diagram

SF-C11 Terminal arrangement diagram     
Terminal Function
A1 +24 V DC
A2 0 V
13-14, 23-24, 33-34 Safety output (NO contact × 3)
41-42 Auxiliary output (NC contact × 1)
X1 Reset output terminal
X2 Reset input terminal (Manual)
X3 Reset input terminal (Automatic)
A Not used
B
T1 Test output terminal
T2 Test input terminal
AUX Semiconductor auxiliary output


Pin layout for safety light curtain connectors

SF-C11 Pin layout for safety light curtain connectors     
Connector pin No. Emitter side connector Receiver side connector
Interlock OSSD 2
+24 V DC +24 V DC
Emission halt OSSD 1
Auxiliary output EDM (External relay monitor)
Synchronization wire + Synchronization wire +
Synchronization wire – Synchronization wire –
0 V 0 V
Shield wire Shield wire

SF-C12

SF4B / SF4B-G series wiring diagram (Control Category 4)

For PNP output (minus ground)
  • Set the two safety light curtain input polarity select switches to the PNP side and connect the FG terminal to the 0 V line.
SF-C12 SF4B series wiring diagram (Control Category 4)
Note: The above diagram is when using manual reset. If automatic reset is used, connect a normally closed type pushbutton switch between T1 and T2 and leave between X1 and X2 open.

For NPN output (plus ground)
  • In the above diagram, set the two safety light curtain input polarity selection switches to the NPN side and connect the F.G. terminal to the + side.
When SF-C12 is connected to the safety light curtain, be sure to use the following mating cable.
SFB-CB05-MU, SFB-CCJ10□-MU


Terminal arrangement diagram

    SF-C12 Terminal arrangement diagram
Terminal Function
FG Frame ground (F.G.) terminal
A2 0 V
A1 +24 V DC
13-14, 23-24 Safety output (NO contact × 2)
31-32 Auxiliary output (NC contact × 1)
FB4 External relay monitor terminal 2
FB3
FB2 External relay monitor terminal 1
FB1
   
Terminal Function
R+ Interference prevention wire – (Receiver side)
R– Interference prevention wire + (Receiver side)
E+ Interference prevention wire – (Emitter side)
E– Interference prevention wire + (Emitter side)
T2 Emission halt input terminal
T1
X2 Automatic reset / manual reset selection terminal
Manual reset: X1 – X2 short-circuited
X1


Pin layout for safety light curtain connectors

SF-C12 Pin layout for safety light curtain connectors
Note: Input and output for pin Nos. ⑪ and ⑫ are not used by this device.
    
Connector pin No. Emitter side connector Receiver side connector
Interlock OSSD 2
+24 V DC +24 V DC
Emission halt OSSD 1
Auxiliary output EDM (External relay monitor)
Synchronization wire + Synchronization wire +
Synchronization wire – Synchronization wire –
0 V 0 V
Shield wire Shield wire
Interference prevention wire + Interference prevention wire +
Interference prevention wire – Interference prevention wire –
(Override input) (Muting input 1)
(Muting lamp output) (Muting input 2)

SF-C13

SF4B / SF4B-G series wiring diagram (Control Category 4)

For PNP output (minus ground)
  • Connect the safety light curtain control outputs OSSD 1 and OSSD 2 to S1 and S2 respectively.
SF-C13 For PNP output (minus ground)

Notes:

1) The above diagram is when using manual reset. If automatic reset is used, disconnect the lead from X2 and connect it to X3. In this case, a reset (RESET) button is not needed.
2) Use a momentary-type switch as the reset (RESET) button.

For NPN output (plus ground)
  • Connect the safety light curtain control outputs OSSD 1 and OSSD 2 to S4 and S2 respectively and ground the + side.
SF-C13 For NPN output (plus ground)

Notes:

1) The above diagram is when using manual reset. If automatic reset is used, disconnect the lead from X2 and connect it to X3. In this case, a reset (RESET) button is not needed.
2) Use a momentary-type switch as the reset (RESET) button.
When SF-C13 is connected to the safety light curtain, be sure to use the following descrete wire mating cable.
SFB-CCB□(-MU), SFB-CC□(-MU)

Terminal arrangement diagram

SF-C13 Terminal arrangement diagram     
Terminal Function
A1 +24 V DC
A2 0 V
S1 to S4 Safety light curtain control output (OSSD) input terminal
AUX Semiconductor auxiliary output
X1 Reset output terminal
X2 Reset input terminal (Manual)
X3 Reset input terminal (Automatic)
13-14, 23-24, 33-34 Safety output (NO contact × 3)
41-42 Auxiliary output (NC contact × 1)

A terminal block is required for wiring of safety light curtain side.


Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)