【Notification of Manufacturer Change for Panasonic Industrial Devices SUNX Products and Panasonic Industrial Devices SUNX Tatsuno Products】
From April 1, 2024, the terms "Panasonic Industrial Devices SUNX Co., Ltd." and "Panasonic Industrial Devices SUNX Tatsuno Co., Ltd."
in this page and in the manuals and other documents to be downloaded will all be replaced with "Panasonic Industry Co., Ltd." and applied accordingly.
Business > Industrial Devices > Automation Controls Top > FA Sensors & Components > Measurement Sensors > Measurement Sensors > Communication Unit for Digital Displacement Sensors SC-HG1 > Specifications
Model No. | SC-HG1-ETC | |
---|---|---|
Applicable regulations | CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations) | |
Compatible controllers | HG-SC□, HG-TC□ | |
Maximum number of connectable controllers |
Maximum of 15 controllers (one master, 14 slaves) per SC-HG1-ETC unit | |
Supply voltage (Note 2) | 24 V DC ±10 %, including ripple 0.5 V (P-P) | |
Current consumption | 100 mA or less | |
Communication protocol | EtherCAT | |
Compliance | IEEE 802.3u (100BASE-TX) | |
Communication speed | 100 Mbps (100BASE-TX) | |
Communication connector | RJ-45×2 | |
Node-to-node distance | 100 m 328.084 ft or less | |
Supported functions | Process data object communication (cyclic communication) Mailbox communication (message communication) CoE Explicit Device Identification Station Alias |
|
Pollution degree | 2 | |
Operating altitude (Note 3) | 2,000 m 6,561.68 ft or less | |
Environmental resistance |
Ambient temperature |
-10 to +45 ℃ +14 to +113 ℉ (No dew condensation or icing allowed), Storage: -20 to +60 ℃ -4 to +140 ℉ |
Ambient humidity |
35 to 85 % RH, Storage: 35 to 85 % RH | |
Voltage withstandability |
1,000 V AC for one min. between all supply terminals connected together and enclosure | |
Insulation resistance |
20 MΩ or higher, using 250 V DC megger between all supply terminals connected together and enclosure | |
Vibration resistance |
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude (10 to 58Hz), maximum acceleration 49 m/s2 (58 to 150 Hz) in X, Y and Z directions for two hours each |
|
Shock resistance |
98 m/s2 (10 G approx.) acceleration in X, Y, and Z directions five times each | |
Grounding method | Casing: Floating type | |
Material | Enclosure : Polycarbonate | |
Communication cable | Category 5e (shielded twisted pair cable recommended) | |
Weight | Net weight: 90 g approx. Gross weight: 150 g appox. |
Notes:
1) | Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20 ℃ +68 ℉. |
---|---|
2) | Power is supplied from a connected controller / master controller. |
3) | Do not use or store in an environment that has been pressurized to an air pressure higher than the atmospheric pressure at 0 m. |
Model No. | SC-HG1-CEF | |
---|---|---|
Applicable regulations | CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations) | |
Compatible controllers | HG-SC□, HG-TC□ | |
Maximum number of connectable controllers | Maximum of 15 controllers (one master, 14 slaves) per SC‑HG1‑CEF unit | |
Supply voltage(Note 2) | 24V DC ±10%, including 0.5V ripple (P-P) | |
Current consumption | 200 mA or less | |
Communication method | CC-Link IE Field | |
Remote station type | Remote device station | |
Network No. setting | 1 to 239 (decimal) [1 to EF (hex)] (0 and 240 or more: Error)(Note 3) | |
Cyclic transmission (Maximum number of links per station) |
RX/RY:128 points each (128 bits), 16 bytes, RWr/RWw: 64 points each (64 words), 128 bytes |
|
Transient transmission | Server function only, data size 1024 bytes | |
Station No. setting | 1 to 120 (decimal) (0 and 121 or more: Error) | |
Communication speed | 1 Gbps | |
Transmission line type | Line, star, (mixing of line and star types is possible), ring | |
Maximum transmission distance | 100 m 328.084 ft | |
Maximum number of units connectable | 121 units (1 master station, 120 slave stations) | |
Cascade connection levels | Maximum 20 | |
Pollution degree | 2 | |
Operating altitude | 2,000 m 6561.68 ft or less(Note 4) | |
Environmental resistance |
Protection | IP40 (IEC) |
Ambient temperature | -10 to +45 ℃ +14 to +113 ℉ (No dew condensation or icing allowed) Storage: -20 to +60 ℃ -4 to +140 ℉ |
|
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH | |
Voltage withstandability |
1,000 V AC for one min. between all supply terminals connected together and enclosure |
|
Insulation resistance |
20 MΩ or more, with 250 V DC megger between all supply terminals connected together and enclosure |
|
Vibration resistance | 10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude (10 to 58Hz), maximum acceleration 49 m/s2 (58 to 150 Hz) in X, Y and Z directions for two hours each | |
Shock resistance | 98 m/s2 acceleration (10 G approx.) in X, Y and Z directions five times each |
|
Material | Enclosure: Polycarbonate | |
Communication cable | Ethernet cable that satisfies 1000BASE-T standard Category 5e or higher (Double-shielded / STP, straight cable)(Note 5) |
|
Weight | Net weight: 100 g approx., Gross weight: 150 g approx. |
Notes:
1) | Where measurement conditions have not been specified precisely, the conditions used were ambient temperature +20 ℃ +68 ℉. |
---|---|
2) | Power is supplied from a connected controller / master controller. |
3) | For the network number setting on this product, convert the network number to hex and set the hex value. |
4) | Do not use or store in an environment that has been pressurized to an air pressure higher than the atmospheric pressure at 0 m. |
5) | Use CC-Link Partner Association recommended cable. |
Model No. | SC-HG1-C | |||||
---|---|---|---|---|---|---|
Applicable regulations | CE Marking (EMC Directive (Note 2), RoHS Directive), UKCA Marking (EMC Regulations (Note 2), RoHS Regulations) | |||||
Compatible controllers | HG-SC□, HG-TC□ | |||||
Maximum number of connectable controllers | Maximum of 15 controllers (one master, 14 slaves) per SC-HG1-C unit | |||||
Supply voltage (Note 3) | 24 V DC ±10 %, including 0.5 V ripple (P-P) | |||||
Current consumption | 80 mA or less | |||||
Communication method | Switchable CC-Link Ver.1.10 or 2.00 | |||||
Remote station type | Remote device station | |||||
Number of occupied station | CC-Link Ver.1.10: 4 stations, CC-Link Ver.2.00: Switchable 2 or 4 stations | |||||
Station No. setting | 1 to 64 (0 and 65 or more: Error) | |||||
Communication speed | 10 Mbps | 5 Mbps | 2.5 Mbps | 625 kbps | 156 kbps | |
Maximum transmission distance |
100 m 328.084 ft |
160 m 524.934 ft |
400 m 1,312.336 ft |
900 m 2,952.756 ft |
1,200 m 3,937.008 ft |
|
Pollution degree | 2 | |||||
Operating altitude | 2,000 m 6561.68 ft or less (Note 4) | |||||
Environmental resistance |
Protection | IP40 (IEC) | ||||
Ambient temperature | -10 to +45 ℃ +14 to +113 ℉ (No dew condensation or icing allowed), Storage: -20 to +60 ℃ -4 to +140 ℉ | |||||
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH | |||||
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure | |||||
Insulation resistance | 20 MΩ or more, with 250 V DC megger between all supply terminals connected together and enclosure | |||||
Vibration resistance | 10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude (10 to 58 Hz), maximum acceleration 49 m/s2(58 to 150 Hz) in X, Y and Z directions for two hours each | |||||
Shock resistance | 98 m/s2 acceleration (10 G approx.) in X, Y and Z directions five times each | |||||
Material | Enclosure: Polycarbonate | |||||
Communication cable | Specified cable (shielded twisted cable) (Note 5) | |||||
Weight | Net weight: 80 g approx., Gross weight: 130 g approx. |
Notes:
1) | Where measurement conditions have not been specified precisely, the conditions used were ambient temperature +20℃+68℉. |
---|---|
2) | If our product will be incorporated in a customer product that will comply with the EMC Directive / EMC Regulations , install our product in a conductive box in accordance with "PLC User's Manual [Published by Mitsubishi Electric Corporation]". |
3) | Power is supplied from a connected controller / master controller. |
4) | Do not use or store in an environment that has been pressurized to an air pressure higher than the atmospheric pressure at 0 m. |
5) | Use only a special-use communication cable that is approved by the CC-Link Partner Association. |
Model No. | SC-HG1-485 | |
---|---|---|
Applicable regulations | CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations) | |
Compatible controllers | HG-SC□, HG-TC□ | |
Supply voltage (Note 2) | 24 V DC ±10 %, Ripple P-P 10 % or less (Within specified power supply voltage range) | |
Current consumption | 40 mA or less | |
Communication method | Two-wire half duplex communication | |
Synchronization method | Start-stop synchronization | |
Communication protocol | MODBUS (RTU / ASCII) / MEWTOCOL-COM | |
Communication speed | 1.2 kbps / 2.4 kbps / 4.8 kbps / 9.6 kbps / 19.2 kbps / 38.4 kbps / 57.6 kbps / 115.2 kbps | |
Electrical characteristics | Complies with EIA RS-485 | |
Number of connectable units |
Host (RS-485) | 1 to 99 units when MODBUS (RTU/ASCII) is used, 1 to 64 units when MEWTOCOL-COM is used |
Controllers | Maximum of 15 controllers (one master, 14 slaves) per SC-HG1-485 unit | |
Stop bit length | 1 bit / 2 bits | |
Parity check | Even / Odd / None | |
Data bit length | 8 bits (RTU) / 7 bits (ASCII) | |
Pollution degree | 2 | |
Operating altitude | 2,000 m 6561.68 ft or less (Note 3) | |
Environmental resistance |
Protection | IP40 (IEC) |
Ambient temperature | -10 to +45 ℃ 14 to +113 ℉ (No dew condensation or icing allowed), Storage: -20 to +60 ℃ -4 to +140 ℉ | |
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH | |
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure | |
Insulation resistance | 20 MΩ, or more, with 250 V DC megger between all supply terminals connected together and enclosure | |
Vibration resistance | 10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude (10 to 58Hz), maximum acceleration 49 m/s2 (58 to 150 Hz) in X, Y and Z directions for two hours each | |
Shock resistance | 98 m/s2 acceleration (10 G approx.) in X, Y and Z directions five times each | |
Material | Enclosure: Polycarbonate | |
Total extension distance | Communication cable: 1,200 m 3,937.008 ft or less between SC-HG1-485 (terminal) and PLC | |
Weight | Net weight: 75 g approx., Gross weight: 120 g approx. | |
Accessories | Termination resistor switching jumper pin: 1 pc. |
Notes:
1) | Where measurement conditions have not been specified precisely, the conditions used were ambient temperature +20℃ +68 ℉. |
---|---|
2 | Power is supplied from a connected controller / master controller. |
3 | Do not use or store in an environment that has been pressurized to an air pressure higher than the atmospheric pressure at 0 m. |