We are sorry, the products have been discontinued. Please refer to the details of the discontinued products and the recommended substitutes list below.
|
|
[Connector type (100/200 V: A-frame to E-frame)]
|
[Connector type (400 V: D, E-frame)]
|
Driver | Applicable motor |
Voltage *1 |
Rated output |
Required Power (at the rated load) |
Circuit breaker (rated current) |
Noise filter (Single phase/ 3-phase) |
Surge absorber (Single phase/3-phase) |
Noise filter for signal | Rated operating current of magnetic (contactor Contact configuration)*2 |
Diameter and withstand voltage of main circuit cable |
Crimp terminal for main circuit terminal block *4 |
Diameter and withstand voltage of control power supply cable |
Crimp terminal for control power supply terminal block |
Diameter and withstand voltage of motor cable *5 |
Diameter and withstand voltage of brake cable |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
MADH MADK |
MSMD MSME MHMD |
Single phase, 100 V |
50 W to 100 W |
approx. 0.4 kVA |
10 A | DV0P4170 | DV0P4190 | DV0P1460 | 20 A (3P+1a) |
0.75 mm2/ AWG18 600 VAC or more |
Connection to exclusive connector | 0.75 mm2/ AWG18 600 VAC or more |
Connection to exclusive connector | 0.75 mm2/ AWG18 600 VAC or more |
0.28 mm2 to 0.75 mm2/ AWG22 to AWG18 100 VAC or more |
Single/ 3-phase, 200 V |
50 W to 200 W |
approx. 0.5 kVA |
DV0P4170/ DV0PM20042 |
DV0P4190/ DV0P1450 |
|||||||||||
MBDH MBDK |
MSMD MSME MHMD |
Single 100 V |
200 W | approx. 0.5 kVA |
DV0P4170 | DV0P4190 | |||||||||
Single/ 3-phase, 200 V |
400 W | approx. 0.9 kVA |
DV0P4170/ DV0PM20042 |
DV0P4190/ DV0P1450 |
|||||||||||
MCDH MCDK |
MSMD MSME MHMD |
Single 100 V |
400 W | approx. 0.9 kVA |
DV0PM20042 | DV0P4190 | |||||||||
Single/ 3-phase, 200 V |
750 W | approx. 1.3 kVA |
15 A | DV0P4190/ DV0P1450 |
|||||||||||
MDDH MDDK |
MDME | Single/ 3-phase, 200 V |
1.0 kW | approx. 1.8 kVA |
DV0P4220 | 30 A (3P+1a) |
2.0 mm2/ AWG14 600 VAC or more |
2.0 mm2/ AWG14 600 VAC or more |
0.75 mm2/ AWG18 100 VAC or more |
||||||
MHME | |||||||||||||||
MGME | 0.9 kW | approx. 1.8 kVA |
20 A | ||||||||||||
MSME | 1.0 kW | approx. 1.8 kVA |
|||||||||||||
MHME | 1.5 kW | approx. 2.3 kVA |
|||||||||||||
MDME | |||||||||||||||
MFME | |||||||||||||||
MSME | |||||||||||||||
MDME | 3-phase, 400 V |
400 W | approx. 0.9 kVA |
10 A | FN258L-16-07 (Recommended component ) |
DV0PM20050 | 20 A (3P+1a) |
0.52 mm2/ AWG20 100 VAC or more |
|||||||
MDME | 600 W | approx. 1.2 kVA |
|||||||||||||
MSME | 750 W | approx. 1.6 kVA |
|||||||||||||
MSME | 1.0 kW | approx. 1.8 kVA |
|||||||||||||
MDME | |||||||||||||||
MHME | |||||||||||||||
MGME | 0.9 kW | ||||||||||||||
MSME | 1.5 kW | approx. 2.3 kVA |
|||||||||||||
MDME | |||||||||||||||
MFME | |||||||||||||||
MHME | |||||||||||||||
MEDH MEDK |
MDME | 3-phase, 200 V |
2.0 kW | approx. 3.3 kVA |
30 A | DV0PM20043 | DV0P1450 | DV0P1460 RJ8035 (Recommended component ) *6 |
60 A (3P+1a) |
0.75 mm2/ AWG18 600 VAC or more |
|||||
MSME | |||||||||||||||
MHME | |||||||||||||||
MFME | 2.5 kW | approx. 3.8 kVA |
|||||||||||||
MSME | 3-phase, 400 V |
2.0 kW | approx. 3.3 kVA |
15 A | FN258L-16-07 (Recommended component ) |
DV0PM20050 | DV0P1460 | 30 A (3P+1a) |
0.52 mm2/ AWG20 100 VAC or more |
||||||
MDME | |||||||||||||||
MHME | |||||||||||||||
MFME | 2.5 kW | approx. 3.8 kVA |
|||||||||||||
MFDH MFDK |
MGME | 3-phase, 200 V |
2.0 kW | approx. 3.8 kVA |
50 A | DV0P3410 | DV0P1450 | DV0P1460 RJ8035 (Recommended component ) *6 |
60 A (3P+1a) |
3.5 mm2/ AWG12 600 VAC or more |
![]() Terminal block M5 |
0.75 mm2/ AWG18 600 VAC or more |
![]() Terminal block M5 |
3.5 mm2/ AWG12 600 VAC or more |
|
MDME | 3.0 kW | approx. 4.5 kVA |
|||||||||||||
MHME | |||||||||||||||
MSME | |||||||||||||||
MGME | |||||||||||||||
MDME | 4.0 kW | approx. 6.0 kVA |
100 A (3P+1a) |
||||||||||||
MHME | |||||||||||||||
MSME | |||||||||||||||
MFME | 4.5 kW | approx. 6.8 kVA |
|||||||||||||
MGME | approx. 7.5 kVA |
||||||||||||||
MDME | 5.0 kW | ||||||||||||||
MHME | |||||||||||||||
MSME | |||||||||||||||
MGME | 3-phase, 400 V |
2.0 kW | approx. 3.8 kVA |
30 A | FN258L-30-07 (Recommended component ) |
DV0PM20050 | DV0P1460 | 60 A (3P+1a) |
![]() Terminal block M4 |
0.75 mm2/ AWG18 100 VAC or more |
![]() Terminal block M3 |
||||
MSME | 3.0 kW | approx. 4.5 kVA |
|||||||||||||
MDME | |||||||||||||||
MGME | |||||||||||||||
MHME | |||||||||||||||
MSME | 4.0 kW | approx. 6.0 kVA |
|||||||||||||
MDME | |||||||||||||||
MHME | |||||||||||||||
MFME | 4.5 kW | approx. 6.8 kVA |
|||||||||||||
MGME | approx. 7.5 kVA |
||||||||||||||
MSME | 5.0 kW | ||||||||||||||
MDME | |||||||||||||||
MHME | |||||||||||||||
MGDH MGDK |
MDME | 3-phase, 200 V |
7.5 kW | approx. 11 kVA |
60 A | FS5559-60-34 (Recommended component ) |
DV0P1450 | DV0P1460 RJ8095 Recommended ( component ) T400-61D (Recommended component ) *6 |
100 A (3P+1a) |
5.3 mm2/ AWG10 600 VAC or more |
![]() Terminal block M5 |
0.75 mm2/ AWG18 600 VAC or more |
![]() Terminal block M5 |
13.3 mm2/ AWG6 600 VAC or more |
|
MGME | 6.0 kW | approx. 9.0 kVA |
|||||||||||||
MHME | 7.5 kW | approx. 11 kVA |
|||||||||||||
MDME | 3-phase, 400 V |
7.5 kW | approx. 11 kVA |
30 A | FN258-42-07 or FN258-42-33 (Recommended component ) |
DV0PM20050 | 60 A (3P+1a) |
0.75 mm2/ AWG18 100 VAC or more |
|||||||
MGME | 6.0 kW | approx. 9.0 kVA |
|||||||||||||
MHME | 7.5 kW | approx. 11 kVA |
|||||||||||||
MHDH MHDK |
MDME | 3-phase, 200 V |
11 kW | approx. 17 kVA |
100 A | FS5559-80-34 (Recommended component ) |
DV0P1450 | 150 A (3P+1a) |
13.3 mm2/ AWG6 600 VAC or more *3 |
![]() Terminal block M6 |
0.75 mm2/ AWG18 600 VAC or more |
![]() Terminal block M4 |
|||
15 kW | approx. 22 kVA |
125 A | 21.1 mm2/ AWG4 600 VAC or more |
||||||||||||
3-phase, 400 V |
11 kW | approx. 17 kVA |
50 A | FN258-42-07 or FN258-42-33 (Recommended component ) |
DV0PM20050 | 100 A (3P+1a) |
0.75 mm2/ AWG18 100 VAC or more |
13.3 mm2/ AWG6 600 VAC or more |
|||||||
15 kW | approx. 22 kVA |
60 A | 21.1 mm2/ AWG4 600 VAC or more |
*1 Select peripheral equipments for single/3phase common specification according to the power source.
*2 For the external dynamic brake resistor, use the magnetic contactor with the same rating as that for the main circuit.
*3 When use the external regenerative resistor of the option (DV0PM20058, DV0PM20059), use the cable with the same diameter as the main circuit cable.
*4 For the ground screw, use the same crimp terminal as that for the main circuit terminal block.
*5 The diameter of the ground cable and the external dynamic brake resistor cable must be equal to, or larger than that of the motor cable.
The motor cable is a shield cable, which conforms to the EC Directives and UL Standards. (G, H-frame only)
*6 Use thses products to suit an international standard.
●About circuit breaker and magnetic contactor
To comply to EC Directives, install a circuit breaker between the power and the noise filter without
fail, and the circuit breaker should conform to IEC Standards and UL recognized (Listed and marked).
Suitable for use on a circuit capable of delivering not more than 5000 Arms symmetrical amperes, below the maximum input voltage of the product.
If the short-circuit current of the power supply exceeds this value, install a current limit device (current limiting fuse, current limiting circuit breaker, transformer, etc.) to limit the short-circuit current.
<Remarks>
・Select a circuit breaker and noise filter which match to the capacity of power supply (including a load condition).
● Terminal block and protective earth terminals
・ Use a copper conductor cables with temperature rating of 75 ℃ or higher.
・ Use the attached exclusive connector for A-frame to E-frame, and maintain the peeled off length of 8 mm to 9 mm.
■Fastening torque list (Terminal block screw/Terminal cover fastening screw)
Driver | Terminal block screw | Terminal cover fastening screw |
|||
---|---|---|---|---|---|
Frame | Terminal name | Nominal size |
Fastening torque (N・m) |
Nominal size |
Fastening torque (N・m) |
F(200 V) | L1, L2, L3, L1C, L2C, B1, B2, B3, NC, U, V, W | M5 | 1.0 to 1.7 | M3 | 0.19 to 0.21 |
F(400 V) | 24V、0V | M3 | 0.4 to 0.6 | ||
L1, L2, L3, B1, B2, B3, NC, U, V, W | M4 | 0.7 to 1.0 | |||
G | L1C, L2C, 24 V, 0 V, DB1, DB2, DB3, DB4, NC | M5 | 1.0 to 1.7 | ||
L1, L2, L3, B1, B2, NC, U, V, W | M5 | 2.0 to 2.4 | M3 | 0.3 to 0.5 | |
H | L1C, L2C, 24 V, 0 V, DB1, DB2 | M4 | 0.7 to 1.0 | M5 | 2.0 to 2.5 |
L1, L2, L3, B1, B2, NC, U, V, W | M6 | 2.2 to 2.5 |
■Fastening torque list (Ground terminal screw/Connector to host controller [X4])
Driver frame | Ground screw | Connector to host controller (X4) |
||
---|---|---|---|---|
Nominal size |
Fastening torque (N・m) |
Nominal size |
Fastening torque (N・m) |
|
A to E | M4 | 0.7 to 0.8 | M2.6 | 0.2±0.05 |
G | M5 | 1.4 to 1.6 | ||
H | M6 | 2.4 to 2.6 |
[Caution]
・ Applying fastening torque larger than the maximum value may result in damage to the product.
・ Do not turn on power without tightening all terminal block screws properly, otherwise, loose contacts may generate heat (smoking, firing).
[Remarks]
・ To check for looseness, conduct periodic inspection of fastening torque once a year.