DSP Relays

Coil data

  • Operating characteristics such as 'Operate voltage' and 'Release voltage' are influenced by mounting conditions, ambient temperature, etc.
    Therefore, please use the relay within ±5% of rated coil voltage.
  • 'Initial' means the condition of products at the time of delivery.

1.Single side stable

Rated coil voltage Operate voltage *
(at 20°C)
Release voltage *
(at 20°C)
Rated operating
current
(±10%, at 20°C)
Coil resistance
(±10%, at 20°C)
Rated operating
power
Max. allowable
voltage
(at 20°C)
3 V DC Max. 80% V of rated coil voltage (Initial) Min. 10% V of rated coil voltage (Initial) 100 mA 30 Ω 300 mW 130% V of rated coil voltage
5 V DC 60.2 mA 83 Ω
6 V DC 50 mA 120 Ω
9 V DC 33.3 mA 270 Ω
12 V DC 25 mA 480 Ω
24 V DC 12.5 mA 1,920 Ω
*square, pulse drive

2.2 coil latching type

Rated coil
voltage
Set voltage *
(at 20°C)
Reset voltage *
(at 20°C)
Rated operating
current
(±10%, at 20°C)
Coil resistance
(±10%, at 20°C)
Rated operating
power
Max. allowable
voltage
(at 20°C)
Set coil Reset coil Set coil Reset coil Set coil Reset coil
3 V DC Max. 80% V
of rated coil
voltage
(Initial)
Max. 80% V
of rated coil
voltage
(Initial)
100 mA 100 mA 30 Ω 30 Ω 300 mW 300 mW 130% V of rated coil voltage
5 V DC 60.2 mA 60.2 mA 83 Ω 83 Ω
6 V DC 50 mA 50 mA 120 Ω 120 Ω
9 V DC 33.3 mA 33.3 mA 270 Ω 270 Ω
12 V DC 25 mA 25 mA 480 Ω 480 Ω
24 V DC 12.5 mA 12.5 mA 1,920 Ω 1,920 Ω
*square, pulse drive

Return to top

Specifications

Item Specifications
Contact
data
Contact arrangement 1 Form A 1 Form A 1 Form B 2 Form A
Contact resistance
(initial)
Max. 30 mΩ (by voltage drop 6 V DC 1 A)
Contact material Au-flashed AgSnO2 type
Contact rating (resistive) 8 A 250 V AC,
5 A 30 V DC
5 A 250 V AC, 5 A 30 V DC
Max. switching power (resistive) 2,000 VA, 150 W 1,250 VA, 150 W
Max. switching voltage 250 V AC, 125 V DC (0.2 A)
Max. switching current 8 A (AC), 5 A (DC) 5 A (AC, DC)
Min. switching load (reference value) *1 10 mA 5V DC
Insulation resistance
(Initial)
Min. 1,000 MΩ
(at 500 V DC, Measured portion is the same as the case of dielectric strength.)
Dielectric strength (initial) Between open contacts 1,000 V AC for 1 min (detection current: 10 mA)
Between contact sets - 2,000 V AC for 1 min (detection current: 10 mA)
Between contact and coil 3,000 V AC for 1 min (detection current: 10 mA)
Surge withstand voltage (initial) *2 Between contact and coil 5,000 V
Time characteristics (initial) Operate (Set) time Max. 10 ms (Max. 10 ms) at rated coil voltage (at 20°C, without bounce)
Release (Reset) time Max. 5 ms (Max. 10 ms) at rated coil voltage (at 20 °C, without bounce, without diode)
Shock
resistance
Functional Min. 196 m/s2 (half-sine shock pulse: 11 ms, detection time: 10 μs)
Destructive Min. 980 m/s2 (half-sine shock pulse: 6 ms)
Vibration
resistance
Malfuntional vibration 10 to 55 Hz (at double amplitude of 2 mm, detection time: 10 μs)
Destructive 10 to 55 Hz (at double amplitude of 3.5 mm)
Expected life Mechanical life Min. 50 x 106 (switching frequency: 180 times/min)
Conditions Conditions for usage,
transport and storage *3
Ambient temperature:
-40 to +60°C
Humidity:
5 to 85% RH
(Avoid icing and
condensation)
Ambient temperature:
-40 to +65°C
Humidity:
5 to 85% RH
(Avoid icing and
condensation)
Ambient temperature:
-40 to +60°C
Humidity:
5 to 85% RH
(Avoid icing and
condensation)
Unit weight Approx. 4.5 g
*1This value can change due to the switching frequency, environmental conditions, and desired reliability level, therefore it is recommended to check this with the actual load.
*2Wave is standard shock voltage of ±1.2 x 50 μs according to JEC-212-1981
*3For ambient temperature, please read"GUIDELINES FOR RELAY USAGE".

Return to top

Expected electrical life

Conditions: Resistive load, switching frequency 20 times/min

Type Rated switching capacity Number of operations
1 Form A 8 A 250 V AC Min. 100 x 103
5 A 30 V DC Min. 100 x 103
1 Form A 1 Form B 5 A 250 V AC Min. 100 x 103
5 A 30 V DC Min. 100 x 103
2 Form A 5 A 250 V AC Min. 100 x 103
5 A 30 V DC Min. 100 x 103

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE SEARCH FAQ

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region



BY PHONE

FAQ


Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)