HE-N Relays

Coil data

  • Operating characteristics such as ‘Operate voltage’ and ‘Release voltage’ are influenced by mounting conditions, ambient temperature, etc.
    Therefore, please use the relay within ± 5% of rated coil voltage.
  • ‘Initial’ means the condition of products at the time of delivery.
Rated coil voltage Operate voltage*
(at 20°C)
Release voltage*
(at 20°C)
Rated operating current
(±10%, at 20°C)
Coil resistance
(±10%, at 20°C)
Rated operating power Max. allowable voltage
(at55°C)
6 V DC Max.75% V of Rated coil voltage
(Initial)
Min.5% V of Rated coil voltage
(Initial)
417 mA 14.4 Ω 2,500 mW 110% V of Rated coil voltage
9 V DC 278 mA 32.4 Ω
12 V DC 208 mA 57.6 Ω
24 V DC 104 mA 230 Ω
*square, pulse drive

Return to top

Specifications

Item Specifications
Contact data Contact arrangement 1 Form A
Contact resistance (initial) Max. 10 mΩ (by voltage drop 5 V DC 20 A)
Max. 3 mΩ (by voltage drop 5 V DC 120 A, reference value)
Contact material AgNi type
Contact rating (resistive) 120 A 490 V AC, 120 A 60 V DC
Max. switching power (resistive) 58,800 VA, 7,200 W
Max. switching voltage 800 V AC, 60 V DC
Max. switching current 120 A
Min. switching load
(reference value)*1
100 mA 5 V DC
Insulation resistance (initial) Min.1,000 MΩ (At 500 V DC, Measured portion is the same as the case of dielectric strength.)
Dielectric strength (initial) Between open contacts 2,000 Vrms for 1 min (detection current: 10 mA)
Between contact and coil 5,000 Vrms for 1 min (detection current: 10 mA)
Surge withstand voltage (initial)*2 Between contact and coil 10,000 V
Coil holding voltage*3 40 to 100% V (at -40 to +55°C)
50 to 60% V (at +55 to +85°C)
Time characteristics (initial) Operate time Max.30 ms (at rated coil voltage at 20°C, without bounce)
Release time Max.10 ms (at rated coil voltage at 20°C, without bounce, without diode)
Shock resistance Functional 98 m/s2 (half-sine shock pulse: 11 ms, detection time: 10 μs)
Destructive 980 m/s2 (half-sine shock pulse: 6 ms)
Vibration resistance Functional 10 to 55 Hz (at double amplitude of 1.0 mm, detection time: 10 μs)
Destructive 10 to 55 Hz (at double amplitude of 1.5 mm)
Expected life Mechanical Min. 106 ope. (at 180 times/min.)
Conditions Conditions for usage,
transport and storage*4
Ambient temperature: -40 to +85°C (When using at +55°C or higher, the coil holding voltage should be 50% V to 60% V)
Humidity: 5 to 85% R.H. (Avoid icing when using at temperatures lower than 0°C.)
Unit weight Approx. 115 g
*1This value can change due to the switching frequency, environmental conditions, and desired reliability level, therefore it is recommended to check this with the actual load.
*2Wave is standard shock voltage of ±1.2 x 50 µs according to JEC-212-1981.
*3Coil holding voltage is the coil voltage after 100 ms following application of the rated coil voltage.
*4The upper operation ambient temperature limit is the maximum temperature that can satisfy the coil temperature rise value.
Refer to in “NOTES” of HE-N relays catalog.

Return to top

Electrical life

Conditions:Resistive load

Type Switching capacity Number of operations
1 Form A 55 A 800 V AC Min. 10 x 103 ope. (at 85°C, ON:OFF = 1 s:9 s)
90 A 490 V AC Min. 10 x 103 ope. (at 85°C, ON:OFF = 1 s:9 s)
120 A 490 V AC Min. 103 ope. (at 85°C, ON:OFF = 1 s:9 s)
120 A 60 V DC Min. 103 ope. (ON:OFF = 1 s:9 s)

Return to top

INSULATION CHARACTERISTICS (IEC61810-1)

Item Characteristics
Clearance/Creepage distance (IEC61810-1) Min. 5.5 mm/8.0 mm
Category of protection (IEC61810-1) RT II
Tracking resistance (IEC60112) PTI 175
Insulation material group III a
Over voltage category III
Rated voltage 800V
Pollution degree 2
Type of insulation (Between contact and coil) Basic insulation
Type of insulation (Between open contact) micro disconnection
*Note: Actual value

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region




Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)