AUTOMATION
CONTROLS

Search
Discontinued
Products



SF Relay Double Contact type

Coil data

  • Operating characteristics such as 'Operate voltage' and 'Release voltage' are influenced by mounting conditions, ambient temperature, etc.
    Therefore, please use the relay within ±5% of rated coil voltage.
  • 'Initial' means the condition of products at the time of delivery.

Contact
arrangement
Rated coil
voltage
Operate
voltage *
(at 20°C)
Release
voltage *
(at 20°C)
Rated operating
current
(±10%, at 20°C)
Coil resistance
(±10%, at 20°C)
Rated
operating
power
Max. allowable
voltage
(at 60°C)
4 poles 2 Form A
2 Form B
5 V DC Max. 75% V of rated coil voltage
(Initial)
Min. 10% V of rated coil voltage
(Initial)
100 mA 50 Ω 500 mW 120% V of rated coil voltage
12 V DC 41.7 mA 288 Ω
24 V DC 20.8 mA 1,152 Ω
48 V DC 10.4 mA 4,608 Ω
60 V DC 8.3 mA 7,200 Ω
8 poles 4 Form A
4 Form B
5 V DC Max. 75% V of rated coil voltage
(Initial)
Min. 15% V of rated coil voltage
(Initial)
100 mA 50 Ω 500 mW 120% V of rated coil voltage
12 V DC 41.7 mA 288 Ω
24 V DC 20.8 mA 1,152 Ω
48 V DC 10.4 mA 4,608 Ω
60 V DC 8.3 mA 7,200 Ω
*square, pulse drive (JIS C 5442)

Return to top

Specifications

Item Specifications
Contact data Contact arrangement 2 Form A 2 Form B 4 Form A 4 Form B
Contact resistance
(initial)
Max. 30 mΩ (by voltage drop 6 V DC 1 A)
Contact material Au-flashed AgSnO2 type
Contact rating
(resistive)
6 A 250 V AC, 6 A 30 V DC
Max. switching
power (resistive)
1,500 VA, 180 W
Max. switching
voltage
440 V AC, 30 V DC
Max. switching
current
6 A
Min. switching load
(reference value) *1
100 mA 5 V DC
Insulation resistance (initial) Min. 1,000 MΩ
(at 500 V DC, Measured portion is the same as the case of dielectric strength.)
Dielectric
strength
(initial)
Between
open contacts
1,300 Vrms for 1 min (detection current: 10 mA)
Between
contact sets
2,500 Vrms for 1 min (detection current: 10 mA)
Between
contact and coil
2,500 Vrms for 1 min (detection current: 10 mA)
Time
characteristics
(initial)
Operate time Max. 30 ms at rated coil voltage (at 20°C, without bounce)
Release time Max. 15 ms at rated coil voltage (at 20°C, without bounce, without diode)
Shock
resistance
Functional 294m/s2 (half-sine shock pulse: 11 ms, detection time: 10 µs)
Destructive 980m/s2 (half-sine shock pulse: 6 ms)
Vibration
resistance
Functional 10 to 55 Hz at double amplitude of 2 mm (detection time: 10 µs)
Destructive 10 to 55 Hz at double amplitude of 2 mm
Expected life Mechanical life Min. 10 x 106 (switching frequency 180 times/min)
Conditions Conditions for usage,
transport and storage *2
Ambient temperature: -40 to +70°C,
Humidity: 5 to 85% RH
(Avoid icing and condensation)
Unit weight Approx. 38 g Approx. 47 g
*1This value is a rough indication of the lower limit at which switching is possible at micro load level.
This value can change due to the switching frequency, environmental conditions, and desired reliability level, therefore it is recommended to check this with the actual load.
*2For ambient temperature, please refer to the "GUIDELINES FOR RELAY USAGE".

Return to top

Electrical life

Conditions: Resistive load, switching frequency 20 times/min

Type Switching capacity Number of operations
2 Form A 2 Form B, 4 Form A 4 Form B 6 A 250 V AC Min. 100 x 103

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region




Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)