Business > Industrial Devices > Automation Controls Top > Components & Devices > Relays / Couplers > Interface Terminal > RT-3 UNIT RELAY (PhotoMOS Power type) /4-POINT TERMINAL (Without relay type) > Rating/Performance
Part No. | Rated input voltage | Operate voltage (at 25°C) |
Release voltage (at 25°C) |
Input current during application of rated input voltage (at 25°C) |
Allowable variation of rated input voltage (at -20 to +55°C) |
---|---|---|---|---|---|
AY34001 | 12 V DC | Max. 9.5 V DC (5.1 V typ.) |
Min. 3.0 V DC (5.0 V typ.) |
6.2 mA typ. | 90 to 110% V of rated input voltage |
AY35001 | |||||
AY34002 | 24 V DC | Max. 15.0 V DC (6.8 V typ.) |
Min. 3.5 V DC (6.5 V typ.) |
6.7 mA typ. | |
AY35002 |
* | This product has a built-in input current limiting resistor; therefore, it is not necessary to externally connect a resistor to the input. The input voltage can be applied directly. |
---|
Part No. | Equipped relay | Max. load voltage | Recommended voltage | Continuous load current | Peak load currant |
---|---|---|---|---|---|
AY34001 | AQZ102 (DC only) |
60 V (DC) | 0 to 30 V (DC) | 2 A (DC) | 9 A (100 ms 1 shot) |
AY34002 | |||||
AY35001 | AQZ204 (AC/DC dual use) |
400 V (DC, AC peak value) |
0 to 200 V (DC) 0 to 125 V (AC) |
0.3 A (DC, AC peak value) |
1.5 A (100 ms 1 shot) |
AY35002 |
*1 | During 4-point simultaneous operation, the rating per point is also as shown in the table above. |
---|---|
*2 | The load current varies depending on ambient temperature. Refer to the “REFERENCE DATA Load current vs. ambient temperature characteristics”. |
Item | Specifications | Condition | |
---|---|---|---|
Dielectric strength (initial) |
Between input and output |
2,000 V AC | for 1 min |
Between different terminals (between relays, both ways) |
1,500 V AC | for 1 min | |
Insulation resistance | Min. 100 MΩ (Measured portion is the same as the case of dielectric strength.) |
Using 500 V DC megger | |
Shock resistance | Destructive shock resistance |
Min. 196 m/s2 | In vertical, horizontal and longitudinal directions |
Destructive vibration resistance |
10 to 55 Hz at double amplitude of 1 mm | In vertical, horizontal and longitudinal directions | |
Use condition | Ambient temperature | -20 to +55°C | Avoid icing and condensation |
Ambient humidity | 35 to 85% RH | Avoid condensation | |
Storage temperature | -30 to +80°C | Avoid icing and condensation | |
Terminal screw fasten torque | 0.3 to 0.5 N·m (3 to 5 kgf·cm) | ||
Cross connection protecting diode | 1 A, inverse voltage 400 V | ||
Unit weight | Approx. 100 g |
*1 | Dielectric strength and insulation resistance are initial values. |
---|---|
*2 | Condensing occurs when the unit relay is exposed to sudden temperature change in a high temperature and high humidity atmosphere. This may cause some troubles like insulation failure of the socket or the PC board. Take care under this condition. |
*3 | Below 0°C, condensing water can freeze and cause socket contact failures and other problems. Take care under this condition. |
Allowable ambient temperature: –20°C to +55°C
|
Allowable ambient temperature: –20°C to +55°C
|
Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)