AUTOMATION
CONTROLS

Search
Discontinued
Products



SF-M Relay

Coil data

・Operating characteristics such as "Operate voltage" and "Release voltage" are influenced by mounting conditions, ambient temperature, etc. Therefore, please use the relay within ±5% of rated coil voltage.
・"Initial" means the condition of products at the time of delivery.

Contact arrangement Rated coil voltage Operate
voltage *1
(at 20°C)
Release
voltage *1
(at 20°C)
Rated operating current
(±10%
at 20°C)
Coil resistance
(±10%
at 20°C)
Rated operating power Max.
allowable
voltage *2
(at 20°C)
2 poles 1 Form A
1 Form B
3 V DC Max. 75% of
rated voltage
(initial)
Min. 10% of
rated voltage
(initial)
90 mA 33.3 Ω 270 mW
(When
input)

100 mW
(When retained)
120 % V
of rated
voltage
5 V DC 54 mA 92.6 Ω
12 V DC 23 mA 533 Ω
16 V DC 17 mA 948 Ω
18 V DC 15 mA 1,200 Ω
21 V DC 13 mA 1,633 Ω
24 V DC 11 mA 2,133 Ω

*1: Square, pulse drive
*2: It is not allowed to apply the continuous maximum voltage to the coil.
In order to obtain the specified performance, please apply the rated voltage.

Return to top

Specifications

Characteristics Item Specifications
Contact Coil arrangement 1 Form A 1 Form B
Contact resistance, max (Initial) Max. 100 mΩ (By voltage drop 6 V DC 1 A)
Contact material RT Ⅱ : Au flashed AgNi type
RT Ⅲ : Au flashed AgSnO2 type
Contact rating (resistive) N.O. contact (5-6 terminal); 6 A 250 V AC, 6 A 30 V DC
N.C. contact (3-4 terminal); 4 A 250 V AC, 4 A 30 V DC
Max. switching power (resistive) N.O. contact (5-6 terminal); 1,500 VA, 180 W (85 W: when load voltage exceeds 30 V DC)
N.C. contact (3-4 terminal); 1,000 VA, 120 W (85 W: when load voltage exceeds 30 V DC)
Max. switching voltage 250 V AC, 125 V DC
Max. switching current N.O. contact (5-6 terminal): 6 A AC, 6 A DC
N.C. contact (3-4 terminal): 4 A AC, 4 A DC
Min. switching load (reference value)*1 1 mA 10 V DC
insulation resistance (initial) Min. 1,000 MΩ at 500 V DC (Measured portion is the same as the case of dielectric strength.)
Dielectric strength (initial) Between open contacts 1,500 Vrms for 1 min (Detection current: 10 mA)
Between contact and coil N.O. contact (5-6 terminal) - coil; 4,000 Vrms for 1 min
N.C. contact (3-4 terminal) - coil; 2,500 Vrms for 1 min
Coil hold voltage*2 60% of rated voltage (-40°C to 85°C)
Time characteristics (initial) Operate time Max. 15 ms (at rated voltage, at 20°C, without bounce)
Release time*3 Max. 10 ms (at rated voltage, at 20°C, without bounce, without diode)
Shock resistance Functional 200 m/s2 (half-sine shock pulse: 11 ms, detection time: 10 μs)
Destructive 1,000 m/s2 (half-sine shock pulse: 6 ms)
Vibration resistance Functional 10 Hz to 55 Hz (at double amplitude of 2.5 mm, detection time: 10 µs)
Destructive 10 Hz to 55 Hz (at double amplitude of 3.5 mm)
Expected life Mechanical life Min. 10 x 106 ope. (at 180 times/min)
Conditions Conditions for usage,
transport and storage*4
Ambient temperature: -40°C to 85°C
Humidity: 5% RH to 85 % RH
(Avoid icing and condensation)
Unit weight Approx. 6.5 g

*1: This value can change due to the switching frequency, environmental conditions, and desired reliability level, therefore it is recommended to check this with the actual load.
*2: Coil holding voltage is the coil voltage after 100 ms from the application of rated coil voltage.
*3: If a diode is connected across the coil in parallel, the release time will be delayed. Check this under actual operating conditions.
*4: For ambient temperature, please read "GUIDELINES FOR RELAY USAGE".

Return to top

Expected electrical life

Condition: Resistive load, at 6 times/min (ON : OFF = 1 s : 9 s)

Type Switching capacity Number of operations
RT Ⅱ, RT Ⅲ N.O. contact (5-6 terminal) 6 A 250 V AC 100 x 103 ope.
6 A 30 V DC 100 x 103 ope.
N.C. contact (3-4 terminal) 4 A 250 V AC 100 x 103 ope.
4 A 30 V DC 100 x 103 ope.

Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)