AUTOMATION
CONTROLS

Search
Discontinued
Products



SC-LG2-CEF-P | IO-Link Master Unit


IO-Link Master Unit

*Photo may vary from actual product.

  • RoHS Compliant This product has been confirmed that it does not contain the 6 substances specified in EU RoHS Directive 2011/65/EU and the 4 substances specified in 2015/863/EU.  


Product Number SC-LG2-CEF-P
Part Number SC-LG2-CEF-P
Details For CC-Link IE Field
Product name IO-Link Master Unit

As of May 07, 2024
Specifications and design of the products are subject to change without notice for the product improvement.

Spec Detail

Item Specifications
Product Number SC-LG2-CEF-P
Part Number SC-LG2-CEF-P
Regulatory compliance CE Marking (EMC Regulations, RoHS Regulations)、UKCA Marking (EMC Regulations, RoHS Regulations)
Supply voltage 24 V DC+10 -15 %, Ripple P-P 10 % or less
Environmental resistance : Ambient temperature -10 to +55 ℃ +14 to +131 ℉ (No dew condensation or icing allowed), Storage: -20 to +70 ℃ -4 to +158 ℉
Environmental resistance : Ambient humidity 35 to 85 % RH, Storage: 35 to 85 % RH
Environmental resistance : Voltage withstandability 1,000 V AC for one min. between all supply terminals connected together and enclosure
Environmental resistance : Insulation resistance 20 MΩ or more with 250 V DC megger between all supply terminals connected together and enclosure
Environmental resistance : Vibration resistance 10 to 150 Hz frequency, 0.75 mm 0.03 in double amplitude (10 to 58 Hz), maximum acceleration 49 m/s2, (58 to 150 Hz) in X, Y, and Z directions for two hours each
Environmental resistance : Shock resistance 98 m/s2 (10 G approx.) in X, Y, and Z directions three times each
Grounding method Power supply connector is equipped with a frame ground (F.G.)
RJ45 connector shield: Directly connected to ground terminal
Internal circuit: C coupling, Casing: Floating type
Limit to the number of flash memory save operations 100,000
(Note) : This product saves settings in internal flash memory.
Material Case: Polycarbonate
Net weight Net weight: 210 g approx., Gross weight: 270 g approx.
Accessories Power supply connector: 1 pc.

CC-Link IE Field specifications

Item Specifications
Current consumption 200 mA or less
Communication method CC-Link IE Field
Remote station type Intelligent device station
Network number setting 1 to 239 (decimal) [1 to EF (hex)] (0 and 240 or more: Error)
Cyclic transmission
[Maximum number of link points per station]
RX/RY: Maximum 112 points (112 bits) / Maximum 112 points (112 bits)
RWr/RWw: Maximum 132 points (132 words) / Maximum 132 points (132 words)
Transient transmission For server function only, message size: 2 kbytes (maximum)
Number of ports 1000BASE-T Ethernet port (RJ45)x 2
Station number setting 1 to 120 (decimal)(0 and 121 or more: Error)
Communication speed 1 Gbps
Communication cable Category 5e or higher Ethernet cables that satisfy the 1000BASE-T standard
(Double shielded twisted pair cable or straight cable)
(Note) : Use a cable recommended by CC-Link Partner Association.
Transmission line type Line type, star type (line/star mixed type also possible), ring type
Maximum distance between stations 100 m 328.084 ft
Maximum number of stations that can be connected 121 (1 master station, 120 slave stations)
Maximum number of stages of cascade connection 20

IO-Link specifications

Item Specifications
Current consumption 150 mA or less (excluding the current consumption of connected IO-Link devices)
Allowable passing current 3 A or less
(Note) : Take care that the total consumption current of connected devices and the unit on the IO-Link side does not exceed the allowable passing current.
Power to devices (L+, L-), digital I/O (C/Q), and digital input (DI) are supplied from IO-Link (+V, -V) on the power supply connector.
Communication method IO-Link V1.0 / V1.1
Number of ports e-CON compliant connector port for IO-Link x 8
Communication speed COM1 (4.8 kbps), COM2 (38.4 kbps), COM3 (230.4 kbps)
Automatically set by IO-Link device
Current supplied to device (L+, L-) Maximum 200 mA per port
(Note) : Take care that the total consumption current of connected devices and the unit on the IO-Link side does not exceed the allowable passing current.
Power to devices (L+, L-), digital I/O (C/Q), and digital input (DI) are supplied from IO-Link (+V, -V) on the power supply connector.
Digital I/O (C/Q) IO-Link mode : Compliance with the IO-Link standard
SIO mode [During input setting] : PNP input (Sink current: Max. 15 mA)
SIO mode [During output setting] : Push-pull output (Drive capacity: Max.100 mA)
(Note 1) : Take care that the total consumption current of connected devices and the unit on the IO-Link side does not exceed the allowable passing current.
Power to devices (L+, L-), digital I/O (C/Q), and digital input (DI) are supplied from IO-Link (+V, -V) on the power supply connector.
(Note 2) : Operation settings for digital I/O (C/Q) and digital input (DI) must be configured with CC-Link IE Field.
If operation settings are not configured, they will not operate.
Digital input (DI) PNP input (Sink current: Max. 15 mA)
(Note 1) : Take care that the total consumption current of connected devices and the unit on the IO-Link side does not exceed the allowable passing current.
Power to devices (L+, L-), digital I/O (C/Q), and digital input (DI) are supplied from IO-Link (+V, -V) on the power supply connector.
(Note 2) : Operation settings for digital I/O (C/Q) and digital input (DI) must be configured with CC-Link IE Field.
If operation settings are not configured, they will not operate.
Communication cable Unshielded
Maximum cable length 20 m 65.617 ft
IO-Link connector e-CON compliant connector (4-pin type)
(Note) : For the connectors for connecting devices to this product, purchase simple wire-press connector (e-CON) CN-EP2 (5 pcs. set) or CN-EP3 (5 pcs. set) or the recommended product.

Return to top

Accessories (Option)

no_image
Product Number CN-EP2
Part Number CN-EP2
Product name Connector
no_image
Product Number CN-EP3
Part Number CN-EP3
Product name Hook-up connector
Dual Display Digital Pressure Sensor [For Gas] DP-100L
Product Number DP-101ZL3-M-P
Part Number DP-101ZL3-M-P
Product Dual Display Digital Pressure Sensor [For Gas]
Details Discrete wire type
Product name Dual Display Digital Pressure Sensor [For Gas] DP-100L


More



Return to top

CONTACT US
If you have any questions, please select the option below to contact us or find answers.
CONTACT BY EMAIL / PHONE FIND LOCAL OFFICE

Return to top

CONTACT US
BY EMAIL
Please click your area to select country or region







BY PHONE

Requests to customers (Automation Control Components & Industrial Device) [Excluding specific product]
Requests to customers (Automation Control Components & Industrial Device) [For specific product]
Requests to customers (FA Sensors & Components [Excluding motors])
Requests to customers (Dedicated to industrial motors)