NC Relays
Sockets and Terminal Sockets
Dimensions
NC2 Flat type
socket |
---|
|
|
NC4 Flat type
socket |
---|
|
|
NC2 Slim type
socket |
---|
|
|
NC4 Slim type
socket |
---|
|
|
NC2
DIN terminal socket |
---|
|
|
|
Types
Type |
Product name |
Terminal connection method |
Type No. |
Part No. |
Main Part No. to be installed |
Standard packing |
Inner carton |
Outer carton |
Flat type socket |
NC2-flat type PC board socket |
PC board |
NC2-JPS |
AW4920 |
AW881 series |
20 pcs. |
200 pcs. |
NC4-flat type PC board socket |
PC board |
NC4-JPS |
AW4940 |
AW884 series |
Slim type DIN terminal socket |
NC2-DIN terminal socket |
DIN rail |
NC2-SFD |
AW4928 |
AW821 series |
20 pcs. |
100 pcs. |
Slim type socket |
NC2-slim type soldering socket |
Solder terminal |
NC2-SS |
AW4922 |
AW821 series |
20 pcs. |
200 pcs. |
NC2-slim type PC board socket |
PC board |
NC2-PS |
AW4924 |
NC2-slim type wrapping socket |
Lead wire |
NC2-WS |
AW4926 |
NC4-slim type soldering socket |
Solder terminal |
NC4-SS |
AW4942 |
AW824 series |
NC4-slim type PC board socket |
PC board |
NC4-PS |
AW4944 |
NC4-slim type wrapping socket |
Lead wire |
NC4-WS |
AW4946 |
Return to top
Rating
Item |
Specifications |
Dielectric strength (initial) |
Each between terminals: 2,000 Vrms for 1 min (detection current:10 mA) |
Insulation resistance (initial) |
Each between terminals: Min. 100 MΩ (at 500 V DC, Measured portion is the same as the case of dielectric strength.) |
Max. continuous carrying current |
Slim type: 5 A 250 V AC, Flat type: 5 A 250 V AC |
Conditions for usage, transport and storage |
Ambient temperature: -50 to +50°C (AW4924, AW4926, AW4928, AW4944, AW4946)
-40 to +70°C (AW4920, AW4922, AW4940, AW4942)
Humidity: 5 to 85% RH (Avoid icing and condensation) |
Return to top
Handling
■ Flat type socket
● Mounting method of relay
-
1) Match the direction of relay and socket.
|
-
2) Insert both ends of the relay firmly, all the way in.
|
-
3) Press the hooks in the direction of the arrows to attach the relay securely.
|
● Removing method of relay
-
1) Pull out the relay after fully releasing both hooks. 2) Take care not to push or spread the hooks more than necessary when installing or removing the relay, because doing so may cause deformation which will prevent the hooks from engaging with the relay, or the hooks may break.
|
■ Slim type DIN terminal socket
● Mounting method of fastening bracket
-
Install the fastening bracket before mounting the relay.
Press the fastening bracket into the terminal socket until it stops and check that the claw has engaged with the terminal socket.
|
● Removing method of fastening bracket
-
Pull out the fastening bracket while pressing the tab with a screwdriver or similar.
|
● Mounting method of relay
-
1) Match the direction of relay and terminal socket.
|
-
2) Insert both ends of the relay firmly, all the way in.
|
-
3) With the included fastening bracket, securely attach the relay.
|
● Removing method of relay
-
1) Pull out the relay after fully releasing fastening bracket. 2) Take care not to push or spread the hooks more than necessary when installing or removing the relay, because doing so may cause deformation which will prevent the hooks from engaging with the relay, or the hooks may break.
|
■ Slim type socket
● Mounting method of relay
-
1) Match the direction of relay and socket.
|
-
2) Insert both ends of the relay securely and all the way until both hooks engage with the mounting grooves.
|
● Removing method of relay
-
1) Pull out the relay while pressing and spreading the hooks. 2) Take care not to push or spread the hooks more than necessary when installing or removing the relay, because doing so may cause deformation which will prevent the hooks from engaging with the relay, or the hooks may break.
|
Return to top
Guidelines for usage
For solder terminal types,
connect terminals as shown in the diagram
to maintain insulation distance.
Return to top
Return to top